ML20009G563

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in IE Insp Repts 50-498/81-01 & 50-499/81-01.Corrective Actions: Procedure GCP-35 Will Be Revised to Provide Protection for Critical Features of in-place Equipment
ML20009G563
Person / Time
Site: South Texas  
Issue date: 05/28/1981
From: Oprea G
HOUSTON LIGHTING & POWER CO.
To: Madsen G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20009G554 List:
References
ST-HL-AE-673, NUDOCS 8108040428
Download: ML20009G563 (5)


Text

-

The Light Company n..

,n iww i,.m im.,x ivoo n.m.mamooi m-n tlay 28, 1981 ST-IIL-AE-673 SFN:

C-0570 51r. G. L. Bladsen, Chief Reactor Projects Branch U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76012

SUBJECT:

SOUTil TEXAS PROJECT ELECTRIC GENERATING STATION RESPONSE TO NRC INSPECTIJN FINDINGS DOCKET NOS. 50-493/81-01 AND 50-499/81-01

Dear 5fr. Stadsen:

The following is our response to your letter dated Btay 5, 1981 re-garding protection of in-place equipment. We concur with your conclusion that construction activities may cause such equipment to be exposed to harsher conditions than those experienced in storage areas. !!owever, it should be noted that for nost items a storage Icvel is specified for the entire item, whereas only certain critical features of the item actually require storage at the specified level.

Since it is not practical to recreate a warehouse environment throughout the plant during construction, it is our intent to provide the same degree of protection for the critical features of in-place equipment as that afforded in storage areas.

This will be accomplished as outlined in our letter of April 13 with the addi-tional condition that procedure GCP-35 (Permanent Plant Blaintenance) will be revised. The revision will require that the Area Blanager or his designee responsible for preparing Equipment Storage and 5aintenance Instruction Record (ES$1IR) cards consider protection of critical features from specifi-cally identified deleterious environments as characterized in ANSI N45.2.2.

An example would be pump / motor assemblies previously stored in a level B warehouse environment.

In the case of in-place protection the critical features of the pump / motor assembly would have the same degree of protection as afforded by the warehouse. This would be done by scaling off internals, protection of machined flange surfaces, tape around seals, energi cd motor heaters, and sealing the motor against entry of water or airborne contami-nation. The protection identified above would not include protecting non-critical features such as the pump casing against airborne or water contam-ination.

8108040428 810716 PDR ADOCK 05(00498 G

PDR

)

e-Ikxiston lpiting & nmrr Conyuny Mr. G. L. Madsen ST-IIL-AE-673 Page 2 In conclusion we feel that this additional information should ade-quately resolve your concerns. The procedure (GCP-35) will be revised on or before June 30, 1981.

If you have any further questions regarding this item, please contact me.

Very truly yours, Q,

G. W. Oprea, Jr.

Executive Vice President GWO:dka

)

Mr. G.L. Madsen ST-HL-AE-673 Ilouston 1.ighting & l'ower Coinpany Page 3 cc:

J. H. Goldberg D. G. Barker C. G. Robertson Howard Pyle R. L. Waldrop H. R. Dean D. R. Beeth J. D. Parsons L. K. English J. W. Briskin R. A. Frazar STP RMS H. S. Phillips (NRC)

J. O. Read (Read-Poland,Inc.)

M. D. Schwarz (Baker & Botts)

R. Gordon Gooch (Baker & Botts)

J. R. Newman (Lowenstein, Newnan, Reis, & Axelrad)

Director, Office of Inspection & Enforcement Nuclear Regulatory Commission Washington, D. C. 20555 M. L. Borchelt Charles Bechhoefer, Esquire President Chairman, Atomic Safety & Licensing Board Central Power & Light Company V. S. Nuclear Regulatory Commission P. O. Box 2121 Washington, D. C.

20555 Corpus Christi, Texas 78403 R. L. Range Dr. James C. Lamb, III Central Power & Light 313 Woodhaven Road P. O. Box 2121 Chapel Hill, North Carolina 27514 Corpus Christi, Texas 78403 R. L. Hancock Mr. Ernest E. Hill Director of Electrical Utilities Lawrence Livermore Laboratory City of Austin University of California P. O. Box 1088 P. O. Box 838, L-123 Austin, Texas 78767 Livermore, Cali fornia 194550 T. H. Muehlenbeck William S. Jordan, III City of Austin Harmon & Weiss P. O. Box 1088 1725 I Street, N. W.

Austin, Texas 78767 Suite 506 Washington, D. C.

20006 J. B. Poston Robert Hager, Esquire Assistant General Manager of Operations Citizens Concerned About Nuclear Power City Public Service Board 5106 Casa Oro P. O. Box 1771 San Antonio, Texas 78'?3 l

San Antonio, Texas 78296 A. vonRosenberg Lanny Sinkin City Public Service Board 2207-D, Nueces P. O. Box 1771 Austin, Texas 78705 San Antonio, Texas 78296 i

Brian E. Berwick, Esquire Jay Guti errez, Esquire Assistant Attorney for the State of Texas Hearing Attorney l

P. O. Box 12548 Office of the Executive Legal Director Capitol Station U. S. Nuclear Regulatory Commission Austin, Texas 78711 Washington, D. C.

20555 6-3-81 _j

ADD TO NOTE #7 The Area Manager or his engineer will physically participate in the weekly inspection.

If the Area Manager is not available for the walk-through, the reason for his not being there will be stipulated on the walk-through report.

NOTE UNDER #2 When generating the in-place protection requirements, the Area Manager or his designee shall consider the following environmental conditions (as applicable):

1.

Sudden temperature changes 2.

Ilumidity and vapors 3.

Physical damage 4.

Airborne contamination 6.

Adjacent construction activities 7.

Inclement weather

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter S

S Houston Lighting & Power S

Docket Nos. 50-498 Company, et al.,

S 50-499 S

South Texas Project S

Units 1 and 2 S

AFFIDAVIT J.H. Goldberg being duly sworn, hereby deposes and says that he is a Vice President of Houston Lighting & Power Company; that he is duly authorized to sign and file with the Nuclear Regulatory Commission the attached r_sponse to the Notice of Violation identified in NRC Inspection Report 81-01; that he is familiar with the content thereof; and that the matters set forth therein are true and correct to the best of his knowledge and belief.

J.H. Goldberg

~

Vice President Nuclear Engineering and Construction STATE OF TEXAS S

S COUNTY OF HARRIS S

Subscribed and sworn to before me. a Notary Public in and l

for Harris County, Texas this3 d day of Cfe 1981.

l

//

psWillettro, f 2.5t4 )

3

        • *%' '/p Angeli K. Self g

~

7 @j Notary ublic in and for t

/

g State of Texas g

_E se

  • m, I

e* y

'1y commission expires:

    • }*****~g/

gg

,,,,,,,mme-

{

._