TENNESSEE VALLEY AUTHORITY Dl71gg CH ATTANOOGA. TENNESSEE 374o1
.a 400 Chestnut Street Tower II
$/ cW -C3]s '
arch 16,1981 v
HTRD-50-518, -519. -5. :, -521/81-05 4M R(([./jI
's 2
!!r. James P. O'Reilly, Director O
0 dl/L g 0 p g -3,
[O W,4 Office of Inspection and Enforcement k g/
-U.S. Nuclear Regulatory Commission
-/
Region II - Suite 3100
,,,/
101 Marietta Street S
g M' 'N /
Atlanta, Georgia 30303
Dear Mr. O'Reilly:
HARTSVILLE NUCLEAR PLANT - REFORTABLE DEFICIENCY - DEFICIENT DRAWING AND DOCUMENT CONTROL - HTRD-50-518, -519, -520, -521/81-05 The subject deficiency was initially reported to ifRC-0IE, Region II, Inspector R. W. Wright on January 27 and February 3, 1981, as HT-G-81-06 deficiencies 1 and 2, respectively.
In compliance with paragraph 50.55(e) of 10 Cr'R Part 50, we are enclosing the final report on the subject deficiency. This nonconformance was resolved along with TVA's response to your letter dated January 30, 1981, Confirmation of Action.
If you have any questions, please call Jim Domer at FTS 857-2014 Very truly yours, TENNESSEE VALLEY AUTHORITY l
L. M. Mills, Manager Nuclear Regulation and Safety Enclosure cc:
Mr. Victor Stello, L1 rector (Enclosure)
Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 l
Si 8107310307 810316 PDR ADOCK 05000518 S
PDR An Ecual 0;:porturuy E:,u' oyer
ENCLOSURE HARTSVILLE NUCLEAR PLANT DRAWING CONTROL PROGRAM AUDIT HT-G-81-06 DEFICIENCIES 1 AND 2 10CFR50.55(e)
~
~-
REPORT NO. 2 (FINAL)
On January 27, 1981, TVA informed NRC-0IE Region II Inspector, R. W.
Wright, of a potentially reportable condition under 10CFR50.55(e) regarding the recurrence of drawing control deficiencies.
This is the final report on this deficiency.
Description of Deficiency The TVA CONST QA Unit at Hartsville performed an audit of the drawings being used on the site. The auditor surveyed 469 drawings being maintained by engineering and crafts pe'sonnel and found 26 drawings which were cut of date ar'i/or superseded by later revisions.
A similar "inding was reported to NRC-0IE Region II on August 15, 1980, in which 30 out of 155 drawings were found.to be superseded.
The auditor also surveyed controlled documents other than construction drawings which are maintained in manuals onsite. This survev revealed that 12 C. F. Braun specifications and associated Engineering Change l
Notices (ECM's) were not.sufficiently controlled in that document recipients did not have up-to-date revisions and the DCU master file contained superseded material.
Safety Implications 5
If any construction er inspection activities were conducted to the requirements of out-of-date or superseded drawings or c icuments, those activities may not conform to current requirements.
Therefore, this could have led to the construction of some plant feature in an incorrect configuration which could Have adversely affected plant safety.
Corrective Action 1.
The Hartsville Site QA Unit conducted a 100-percent audit of safety-related site-issued dracings. This audit revealed that out of approximately 40,000 drawings, 1155 superseded d.awings were being held by engineering and quality control inspection personnel. An extended survey of other selected controlled documents was also conducted.
All superseded drawings and J
documents have been replaced with current revisions.
. ~
r 2.
Of the 1155 superseded drawings identified under action item 1,16 were identified as being in use. Each case is described below.
I 4KE5603-2K-02 R3 - This drawing was used for acceptance (1 cor' -
inspe:tions on P:op-fabricated items. The 1
assigned to change effected by revision 4 involves a QA Civil Unit) feature on the Mk. No. 4-frames. None of these j
I frames were inspected during the time that this superseded drawing was in use.
1 S-515221FP1-1 R0 - These were used to fabricate a single support.
l S-515221FP1-2 R0 The support was installed on August 18, 1980.
S-525221FP1-3 R0 These drawings were revised on October 26, (4 copies each-1980. Sequence Control Charts are being I
assigned to changed to modify this support as required.
STRIDE Project Engineering Hanger Unit)
S-514A44FP1-1 RO '- Member size was changed by revision 1 to e S-514A44FP1-2 RO smaller size. Since we are still fabricating (1 copy each -
and installing this support, t' design change assigned to will be implemented.
l STRIDE Project l
Engineering Hanger Unit) i l
S321200AP2 R1 - No changes in the fabrication or installation of l
(1 copy -
this supoort are necessitated by this change assigned to STRIDE Project Engineering i
Han6er Unit) 3 A team consisting of GA engineers from the staff of TVA's Office of Engineering Design and Construction (OEDC) and the Quality 1
i Assurance Branch of the Division of Construction (CONST) conducted an investiration to determine why the brea'<down in drawing control occurred after full compliance was reported to have been achieved as of October 8,1980. The investigation was f
conducted on February 12-14, 1981. The following is a summation of the results of this investigation.
\\
(a) No individual or organization was responsible for the entire drawing control process from receipt of a drawing until it was retrieved.
I (b) There were too many individuais and stations where groups of controlled drawings were located which contributed to the increase in the number of drawings.
j i
+
I
-_=
(c) No restraints were placed on personnel requesting drawings or
-complete sets of drawings from the Document Control Unit which also contributed to the increase in the number of drawings.
(d) Vendor drawings were not adequately identified and controlled.
( f) Construction working drawings were not identified as controlled drawings.
(g) Field Change Requests (FCR's) were not being incorporated on
+
C. F. Braun drawings.
(b) The Drawi43 Index ras not maintained in an accurate status.
4.
At1 TVA construction site QA units were directed to conduct audits ta determine if the Hartsville drawing control problems existed at other TVA nuclear facilities. All audit scopes were expanded beyond drawing control in order to evaluate other areas of document control,'i.e., Field Change Requests (FCR's),
Construction Engineering Procedures (CEP's), Quality Control Instructions (QCI's), etc. With the exception of Hartsville, there were no audit findings evaluated and deemed "significant."
Line and CA management reviewed the audit and investigation findings on February 18, 1981. No document control procedure changes were necessary for Sequoyah, Watts Bar, or Bellefonte.
The drawing control procedure did require adjustments for Hartsville, Phipps Bend, and Yellow Creek Nuclear Plants.
A revision to Construction Engineering Procedure, CEP-6.01, " Drawing Control,," was drafted on February 26, 1981, and is intended to prevent recurrence of the causes of this deficiency listed in part 3 above. For all plants, line management emphasis is being implemented to achieve and maintain full compliance with procedural requirements of drawing and document control, and l
accelerated auditing will be used to assure compliance. We believe that the program adjustments, line management emphasis, direct supervision, employee training and accelerated auditing will preclude recurrence of significant deficiences in our drawing l