Forwards Review of Soil-Structure Interaction & Seismic Analysis of Category I Structures,South Tx Project,Units 1 & 2. Rept Supports Util View That Use of Finite Element Analysis Technique Was Appropriate
ML20009D743
Person / Time
Site: South Texas  
Issue date: 07/21/1981
From: Goldberg J
HOUSTON LIGHTING & POWER CO.
To: Eisenhut D
Office of Nuclear Reactor Regulation
Shared Package
ML20009D744 List:
References
ST-HL-AE-704, V-0100, V-100, NUDOCS 8107240314
Download: ML20009D743 (4)


Text

.

The Light c o m P u y iimes,em i.ish,,mx & i.e <,

i.o.isexi2oo iime,,mm.rexm,21ooi 17is,22s.92ii July 21, 1981 ST-HL-AE-704 SFN:

V-0100 M

N h( D

/m ds o,73e o

Division of Licensing u.$ #Ngg Mr. Darrell G. Eisenhut l

AP c

Nuclear Regulatory (,onmission h'

N/

Washington, D. C.

20555 N% 'Qhq\\ d '

/.

References:

(1)

NRC Meeting Minutes dated March 3, 1975 (2)

NRC FSAR Questions 130.11 and 12 (3)

NRC Meeting Minutes dated May 23, 1979 (4)

NRC Meeting Minutes dated October 11, 1979 (5) HL&P Letter Clarifying Reference 4 dated November 13, 1979 (6) HL&P Letter dated May 16, 1980

Dear Mr. Eisenhut:

South Texas Project Units 1 & 2 Docket Nos. STN 50-498, STN 50-499 Soil Structure Interaction The purpose of this letter is to transmit the attached consultants reports on soil structure interaction (SSI) and to outline the HL&P position regarding the SSI analysis technique used for the design of the South Texas Project.

During the review of the Preliminary Safety Analysis Report (PSAR), HL&P proposed to meet a new Staff position using the finite element technique for SSI.

On February 13, 1975, a meeting (ref. 1) was held with the Staff to resolve the details of the criteria and procedures to be used and documented in the PSAR.

The Safety Evaluation Report documented the acceptance of this approach. On April 15, 1979, the Staff requested (ref. 2) conparative alternate analysis techniques be provided.

Following the receipt of these questions, meetings were held by the Staff and HL&P (including consultants) on May 10, 1979, September 18, 1979, and July 18, 1980 to discuss both the approach and the results of numerous SSI studies (References 3, 4, 5, & 6).

In January,1981, HL&P commissioned two review task force committees of consultants to review the finite element methodology as employed at STP.

One committee has been involved in the SSI studies since 1975 and was composed of STP SSI Project Team and Project Consultants. The second committee was composed of consultants not previously associated with STP.

The individual members of

\\

the respective committees were:

7 8107240314 810721 PDR ADOCK 05000498 A

PDR L

~

4 Ilouuon Lighting & Power Company July 21, 1981 ST-HL-AE-704 SFN: V-0100 Page 2 Project Team Woodward-Clyde Consultants 1

Dr. C. Y. Chang Dr. I. M. Idriss Brown & Root Dr. James P. Lee Project Consultants

~Dr. Eduardo Kausel Associate Professor of Civil Eng. M.I.T.

Dr. John Lysmer Professor of Civil Engineering, Univ. of Calif., Berkeley Dr. H. Bolton Seed Professor of Civil Engineering, Univ. of Calif., Berkeley Indet erdent Consultant Team f.r. Anil K. Chopra Departmeqt of Civil Engineering, Univ. of Calif., Berkeley Dr. Jose M. Roesset Department of Civil Engineering, Univ. or Texas, Austin Dr. Robert V. Whitman Department of Civil Engineering, M.I.T.

Each connittee was charged individually with reviewing the following considerations:

1) the applicability of the finite element method for soil-structure interaction analyses to the STP site 2) the applicability of the procedures used in the seismic analysis of i

Category 1 structures 3) a review of the sources of conservatism for adeouacy, including input motion 4) conservatism of the results A summary of the respective findings and conclusions of the two conmittees are contained below:

Project Team Task Force Findinos and Conclusions "The finita element method used in the analysis of soil-structure inter-action is an applicable and appropriate method for assessing soil-structure interaction effects at the STP. Based on examinations of various i

Ilouston Lighting & Power Company July 21, 1981 ST-HL-AE-704 SFN: V-0100 Page 3 sources 0 conservatism, it is concluded that the results of the SSI analysis and the seismic structural analyses are very conservative for the design of the Category 1 structures and the subsystems at the STP site."

Independent Consultant Team Task Force Findings and Conclusions "The two-dimensional finite element method used by WCC was a generally accepted procedure in 1975. From our examination, it is clear that great care was takan in the development of the model for the soil profile and of the finite element representation, and in the selection of the parameters for the model. All of the regulatory requirements concerning uncertainty in soil properties and concerning the variations of ground motions with depth were satisfied. The Consultants have examined carefully a number of aspects Of the results, particular1v the computed response spectra at the base of the Reactor Containment Building. These results appeared to be quite reasonable for the depth of embedment and the soil properties and to be consistent with the natural frequencies of the building."

"In short, if this project were starting up fresh today, the Consultants would accept essentially the same types of analysis as that completed by WCC."

"Taking all considerations into account, the Consultants believe that the procedures used for analysis of soil-structure interaction and dynamic analysis are appropriate for the STP, and - if implemented prcperly or conservatively - should lead to forces and floor response spectra which are conservative for use in design. Where computed results were examined in detail, they appeared to be either correct or conservative, suggesting appropriate implementation for at least those parts of the analysis."

In view of the findings represented in the attached reports, HL&P is confident in the belfef that the finite element analysis technique, utilized to establish the STP soil / structure interaction for seismic ground motions, was appropriate. HL&P does not believe that other methods of analysis for STP soil / structure interaction is either necessary or warranted.

Very truly yours, J. H. Goldberg Vice President Nuclear Engineering & Construction JGW/amj Attachment

.e flouston Ligluing & Power Company cc:

J. H. Goldberg July 21, 1981 J. G. Dewease ST-HL-AE-704

0. G. Barker SFN: V-0100 C. G. Robertson Page 4 Howard Pyle R. L. Waldrop

.H. R. Dean D.'R. Beeth J. D. Parsons J. W. Williams J. W. Briskin J.

E.~ Geiger-STP kMS H. S. Phillips (NRC)

-J. O. Read (Read-Poland,Inc.)

M.-D..Schwarz (Baker & Botts)

R. Gordon Gooch (Baker & Botts)

J..R..Newman (Lowenstein, Newman, Reis, & Axelrad)

Director, Office of Inspection & Enforcement Nuclear Regulatory Commission Washington, D. C. 20555 P. L. Range /G. W. Muench Charles Bechhoefer, Esquire Central Power & Light Company Chairman, Atomic Safety & Licensing Board

-P. 0.. Box _2121 U. S. Nuclear Regulatory Conmission Corpus Christi, Texas 78403 Washington, D. C.

20555 R. L.-Hancock/r. H. Muehlenbeck Dr. James C. Lamb, III City of Austin 313 Woodhaven Road P. O. Box 1088 Chapel Hill, North Carolina 27514

Austin, Texas 78767 J. B. Poston/A. vonRosenberg Mr. Ernest E. Hill City Public Service Board Lawrence Livermore Laboratory P. O. Box 1771 University of California San Antonio, Texas 78296 P. O. Box 808, L-123 Livermore, California 94550 Brian.E. Berwick, Esquire William S. Jordan, III Assistant Attorney for the State of Texas Harmon & Heiss P. O. Box 12548 1725 I Street, N. W.

Capitol Station Suite 506 Austin, Texas 78711 Washington, D. C.

20006

-Lanny Sinkin' Citizens for Equitable Utilities, Inc.

Citizens Concerned About Nuclear Power c/o Ms. Peggy Buchorn 5106 Casa Oro-Route 1, Box 1684

' San Antonio, Texas 78233 Brazoria, Texas 77422 LJay Gutierrez, Esquire Hearing Attorney

. 0ffice of the Executive Legal Director U. S. Nuclear Regulatory Commission Washington, D. C..

20555 Revision Date 7-22-81

. - -. - - - -. - - - -