,6% Commonwealth Edison

]

^

) On3 First Nitional Plazt. Chic go, Illinois C ; Address Reply to: Post Office Box 767 l\\

/ Chicago, I;linois 60690 July 15, 1981 1?;

Qg Directorate of Inspection and

>hy, h(g\\>g '4s Mr. James G. Keppler, Director 0

c *cp

'J' L- }

hv c/

Enforcement - Region III h2 U.S. Nuclear Regulatory Commission C\\

Sv d

799 Roosevelt Road E'x Y [6 ff Glen Ellyn, IL 60137 f

g/

N9' di

Subject:

LaSalle County Station Units l'e/ 1L2ui i s ct '

Motor Terminal Block Voltage Rating Limitorque Valve Controls 10 CFR 50.55(e) Interim Report LSCS 50.55(e) #81-01 NRC Docket Nos. 50-373/374 Reference (1):

L. O. DelGeorge letter to J. G. Keppler dated February 20, 1981

Dear Mr. Keppler:

The purpose of this transmittal is to update information provided in Reference (1) relative to the subject motor terminal block modification program.

The current schedule is delineated below:

Phase I:

Inspection Unit 1:

Complete by July 27, 1981 Unit 2:

Complete by September 22, 1981 Phase II:

Installation of bolted, lug L lug taped termination Unit 1:

Complete bs (;ti.Mr 5, 1981 N

Unit 2:

Complete $.,

olier 2, 1981 5

As of June 19, 1981, 179 (50%) ot the Limitorque Valve

/h Controls in Unit I had been inspected.

Of the 179 inspected, 136 will require the motor circuit terminal block to be replaced with a

-bolted lug to lug taped termination.

These initi'.ol results led to the extended installation schedule.

A follow-up report on the progress of the replacement effort on Unit I will be submitted by September 15, 1981.

At that time the impact if any on the expected fuel load date for Unit 1 will be addressed.

6107240073 810715 N

rg 13 PDR ADOCK 05000373 S

PDR

. In the event you have any further questions in this regard, please direct them to this office.

Very truly yours, j}w~~,,(' h<

f L.O. DelGeorge Director of Nuclear Licensing cc:

Director of Inspection and E.forcement, Washington, DC RIII Inspector - LaSalle 2294N

,