Responds to IE Bulletin 81-02.Westinghouse Informed Util That 12 W-EMD Mfg Valves Requiring Closure at Differential Pressures Greater than Limits Set Forth in Table 1 of Bulletin Have Been Identified.List of Affected Valves Encl
ML20009B587
Person / Time
Site: Marble Hill
Issue date: 07/07/1981
From: Shields S
PSI ENERGY, INC. A/K/A PUBLIC SERVICE CO. OF INDIANA
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
IEB-81-02, IEB-81-2, NUDOCS 8107160341
Download: ML20009B587 (3)


Text

_ _ _ _ _ _ _ _ _ _ _ _.

e PUBLIC SERVICE INDIANA S. W. Shields Senior Vice Presdent -

Nuclear Division Y

Mr. James G. Keppler, Director Docket Nos.:

STN 50-546 U.S. Nuclear Regulatory Commission STN 50-547 Region III Construction Permit Nos.:

799 Roosevelt Road CPPR - 170 Glen Ellyn, Illinois 60137 CPPR - 171 Marble Hill Nuclear Generating Station - Units 1 and 2 IE P211etin No. 81-02

Dear Mr. Keppler:

In response to IE Bulletin No. 81-02, Public Service Company of Indiana, Inc.

(PSI) has been informed by Westinghouse that twelve (12) W-EMD manufactured valves which require closure at differential pressures greater than the limits set forth in Table 1 of the subject bulletin have been identified. These valves are listed in the attached chart with the additional information requested.

Westinghouse has not yet completed the testing and redesign program to the point of choosing a best modification for each valve type.

PSI currently plans to return the identified valves to Westinghcuse for modification.

Efforts are now underway by Westinghouse to develop a schedule for valve modifications that is consistent with the need dates of their customers.

The PSI manpower expended in the review and p-sparation of this response was approximately 22 manhours.

It is estimated ~.nat corrective actions will necessitate an additional 25 to 30 PSI manhours.

$Eol s

/(

O g 10 8107160341 810707

{DRADOCK 05000546

'. Indiana 47162 812. 289.1000 PDR

PUBUC SERVICE INDIANA James G. Keppler July 7, 1981 If you have any questions regarding this matter, please contact me at your conve nienc e.

PUBLIC SERVICE COMPANY OR INDIANA, INC.

By

~

S.W. Shields Senior Vice President-Nuclear Division STATE OF INDIANA

)

) SS:

COUNTY OF JEFFERSON )

Subscribed and sworn to before me, a Notary Public, in and for said county and state, this 7th day of July, 1981.

Cth__i10,k 0bhb amdA

( Martha beoe u Danntr) Notary Public My Commission Expires:

4 J 1CLLA I3 l983 J

My County of Residence:

Le iT le r[0_ n cb LY/dks Director, Office of Inspection and Enforcement cc:

U.S. Nuclear Regulatory Commission Washing ton, D.C.

20555 E. R. Schweibinz, P.E.

J. J. Harrison

E e

Westinghouse Valves Affected By IE Bulletin No. 81-02 Planned for use on Marbic 11111 Nuclear Units 1 and 2 PLANNED SERVICE PSI IDENTIFICATION WESTINC110USE MAX. AP (PSI) AT

  • POTENTIAL IDENTIFICATION WilICil REQUIRED SAFETY TO CLOSE CONSEQUENCES Power Operated Relief 1RY8000A-1 3-GM88FN11 2500 1

Valve Block Valve IRY8000B-2 2RY8000A-1 2

2RY8000B-2 CVCS Charging Line Isolation ICV 8105 3-GM78FN 2750 2,3 2

1CV8106 2CV8105 2CV8106 Safety Injection Pump ISI8821A-1 4-GM77FH 1500 2,3 Discharge Crossconnect 1SI8821B-2 Isolation 2SI8821A-1 2SI8821B-2

  • Potential Safety Consequenses 1.

Potential incomplete isolation of pressurizer PORV.

2.

Potential cavitation of centrifugal charging pump or safety injection pump due to operation beyond maximum runout flow.

3.

Potential degradation of safety injection flow below values given in SAR.

ATTACliMENT