\\ c' PRAIRIE ISLAND INCLEAR GENERATING PLANT Docket No. 50-282 License No. DPR-42 50-306 DPR-60 Environmental Event Report 81-01 Under TS B-5.4.2.A, we are required to report as an Environmental Event, when a protection condition is exceeded. TS B-2.4.1 specifies that during chlorination periods, the total residual chlorine concentration at the outf all of the circulating water system shall not cxceed 0.05 ppm for a chlorination cycle of not more than two hours per day.
The daily chlorination cycle on June 4, 1981 extended for i duration of 126 minutes due to a malfunction of the timer.
As correction cccion a new electronic timer with more precise time control has been installed with a setting of 110 minutes per day.
~
W E C Ward, PE Manager-Nuclear Environmental Services ECW/jh Director, NRR c/o DSB (17) cc Resident Inspector MPCA Attn: J W Ferman 8107070360 010702~'