ML20008F968

From kanterella
Jump to navigation Jump to search
Forwards LER 81-009/03L-0
Date released: 01/22/2020 Download: ML20008F968


LER 81-009/03L-0:on 810407,while 1A RHR Svc Water Pump Being Run for Packing Adjustment,Pump Failed to Meet Flow Requirements of 3,500 Gpm at 198 Psig.Caused by 3 Pieces of Wood in Pump Suction.Packing Sleeve & Bearings Replaced
ML20008F972
Person / Time
Site: Quad Cities 
Issue date: 04/28/1981
From: Buss R
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20008F972 (1)
Forwards LER 81-009/03L-0
ML20008F967
Person / Time
Site: Quad Cities 
Issue date: 04/28/1981
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: KEPPLER J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20008F967 (1)