Submits NPDES Noncompliance Notification.Sewage Treatment Plant Effluent Samples Collected on 810127-0217 Revealed Less than Min 1.0mg/1 Dissolved Oxygen.Cause Is Unknown. Treatment Efficiency Was Reduced by Ambient Temp Decreases
ML20008E674
Person / Time
Site: Sequoyah  
Issue date: 03/03/1981
From: Elashry M
TENNESSEE VALLEY AUTHORITY
To: Patrick J
GEORGIA, STATE OF
References
NUDOCS 8103090409
Download: ML20008E674 (2)


Text

.

t

)'

)

TENNESSEE VALLEY AUTHORITY Mannes. TENN&sses 37828 215 Natural Resources Building NARCH 3

198]

i I

Mr. James R. Patrick, Jr., Chief j

Compliance Section, Water Enforcement Branch Environmental Protection Agency, Region jIV i

345 Courtland Street j

F Atlanta, Georgia 30365

Dear Mr. Patrick:

NOTIFICATION OF NONCOMPLIANCE WITH EFFLUENT LIMITATIONS - NPDES PERMIT N0. TN0026450 - SEQUOYAH NUCLEAR PLANT

[

Description of the discharge--Discharge 002 - Sewage treatment plant effluent.

l Samples collected on the following dates contained less than the minimum i

1.0 mg/l dissolved oxygen.

t Date Dissolved Oxygen mg/l j

i 1 81 0.6 1-28-Si 0.6 l

1-30-81 0.5 2 1-81 0.9 i

2-2-81 0.5 i

2-3-81 0.7 2-17-81 0.7 l

Samplu collected on February 16 and 18,1981, had pH values less than the 4

min. mum pH limit of 6.0 units. Both samples had pH values of 5.8 units.

l l

Cause and period of the noncompliance--Ine cause of the noncompliance is i

unknown; however, we believe that decreases in ambient temperature and in i

organic and bydraulic loadings (because of a decrease in the number of personnel), ond improperly set air cycles reduced the plant's treatment efficiency.

Steps taken to reduce, eliminate, and prevent recurrence of the noncomply_ipi discharge--Plant operations have been reviewed and air cycles have boca changed l

to try to correct the low dissolved oxygen problem. The pH was increased by adding sodium bicarbonate to the plant.

Sincerely, j

i Mohamed T. El-Ashry, Ph.D.

Director of Environmental Quality i

cc:

See page 2 8103090409 An Equal Opportunity Employer

.. MAP.CH 3

1981 Mr James R. Patric!;, Jr.

cc: Tennessee Depart:;'ent of Public 'iealth Division of F.'ater Quality Contial c21 Cordell Hull Building Nashville, Tennessee 37219 Mr. Harold E. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Co;;ciission 7920 Norfolk Avenue Washington, DC 20555 fir. Ja es P. O'Reilly, Director Of fice of Inspection and Enforce:.:ent U.S. l,uclear Regulatory Comission i

Region II - Suite 33C3,101 arietta Street Atlanta, G orgia 30303 h

i I

i l

_