ML20008E040

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 80-15, Possible Loss of Emergency Notification Sys (ENS) W/Loss of Offsite Power. Insp Conducted on 800627 to Verify That ENS Is Powered Onsite
ML20008E040
Person / Time
Site: Arkansas Nuclear  
Issue date: 09/03/1980
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
1-090-02, 2-090-02, IEB-80-15, NUDOCS 8010240112
Download: ML20008E040 (2)


Text

e e'

,(

r ARKANSAS POWER & LIGHT COMPANY PCST OFFICE BOX 551 LITTLE ROCK. ARKANSAS 72203 C501) 371-4000 September 3,1980 1-090-02 2-090-02 l

Mr. K. V. Seyfrit Director Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011

SUBJECT:

Arkansas Nuclear One - Units 1 and 2 Docket Nos. 50-313 and 50-365 License Nos. DPR-51 and NFF-5 IE Bulletin 80-15 (File: 1510.1, 2-1510.1)

Gentlemen:

The following information is provided in response to IE Bulletin 80- 15.

Each response is numoered in accordance with the bulletin ques ti ons.

1.

In compliance to your request, after re:eiving and reviewing the subject Bulletin, an irspection was mace on June 27, 1980, to verify that our Emergency Notification System is powered using on-site power as described in the two enclosures af Inis I-E Bulletin.

2.

Our ENS station packages are fed by an inverter which is backed up by a battery bank and a diesel gei;?rator.

3.

A test was conducted to verify that all extensions of the ENS located at our facility remained fully operable from the facility to the NRC Operations Center upon a loss of offsite power to our facility.

Tnis was accomplished by removing all A.C. power to the inverter.

8o10240#1 Q

- - 00 2 sous-u ~ 1,ee eve e.-

r Mr. K. V. Seyfrit September 3,1980 r

4.

Our Emergency Notification System is connected to an inverter which is backed up by automatic transfer Therefore, a to a battery (and a diesel generator.24) hour notification to the NRC Op twenty-four Center was not required.

5.

The Operations Department at AN0 has prepared and

-issued a standing order #46 Rev. I which requires notification to the NRC Operations Center within one hour of the time that one or more extensions of our ENS located at our facility is (are) found to be i noperable.

As requested by the cover letter to the subject Bulletin, approximately twenty (20) nenhours were expended to review, inspect and prepare this res ponse.

Very truly ycurs,

  • bMN[.f David C. Trir.ble Manager, Licensing DCT/GAC/lp ikh cc:

Mr. Victor Stello, Jr., Director Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D.C.

20555 L.