Responds to NRC Re Violations Noted in IE Insp Repts 50-352/80-12 & 50-353/80-11.Corrective Actions: Memorandum Issued Directing That No Matl Substitutions Be Made to Permanent Plant Hangers W/O Prior Approval
ML20008D950
Person / Time
Site: Limerick  
Issue date: 09/03/1980
From: Kemper J
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20008D949 List:
References
QUAL-1-2-2-1, QUAL-1-2-2-2, NUDOCS 8010230711
Download: ML20008D950 (1)


Text

'

PHILADELPHIA ELECTRIC COMPANY 2301 MARKET STREET P.O. BOX 8699 PHILADELPHI A PA.19101 JOHN 5.KEMPER VIC E #R ESID E NT g,

g I

Mr. Boyce Grier, Director United States Nuclear Regulatory Commission Office of Inspection Enforcement Region I 631 Park Avenue King of Prussia, PA 19406 i

Subject:

USNRC IE Region I Letter, dated March 12, 1980 RE: Site and Office Inspection of November 29-30 and December 3-21, 1979 (a) Inspection Report #50-352/79-12 and 50-353/79-11 Limerick Generating Station, Units 1 and 2 l

(b) PECO Letter to the NRC, dated April 10, 1980 l

(c) PECO Letter to the NRC, dated June 10, 1980 l

l File:

QUAL 1-2-2-1 (79-12) l QUAL 1-2-2-2 (79-11)

I i

Dear Mr. Grier:

l In response to the questions raised regarding the Philadelphia l

Electric Company response to Item D of reference (a), we have l

the following additional information:

With regard to the question as to which sampling plan in MIL Standard 105D was being employed, we are using inspection level II from Table I and Table II-A - single sampling plans for normal inspection.

Use of this plan necessitates an AQL of less than 0.010 since no rejects will be acceptabic.

l l

A memorandum was issued to the superintendents that was required to be read by every individual responsibic for hanger l

installations.

The memorandum directed that no material j

substitutions be made to any permanent plant hangers without prior engineering approval.

i Should you have any additional questions regarding this response, we would be pleased to discuss them with you.

Sincerely, pa n

80102307/[

.-