l A

pucg g

jo UNITED STATES

.y

>s.r# g NUCLEAR REGULATORY COMMISSION g

WASHINGTON, D. C. 20555 t

/. j 8

%,*....,e FEB 111990 MEMORANDUM FOR(T. Novak, Chief, Reactor Systems Branch Division of Systems Safety FROM:

V. S. Noonan, Chief. Engineering Branch Division of Operating Reactors

SUBJECT:

TMI-1, EMERGENCY PRESSURE-TEfiPERATURE LIMITS Plant Name: TMI-l NSSS Vendor: B&W Docket No.: 50-289 Operating Reactors Branch and Project Manager: ORS-4, D. Dilanni Technical Branch Involved:

Engineering Branch Due Date: February 11, 1980 Review Status: Complete Memorandum from G. Mazetis to V. Noonan dated January 29, 1980, transmitted proposed pressurization' limitations for TMI-1 during emergency conditions.

These limits are proposed for two EFPY of operation beyond June 1979.

Since TMI-l has operated for about 31/2 EFPY, this would make these limits effective for about 5 1/2 EFPY.

We have reviewed these limits and conclude that they are acceptable for 5 EFPY.

The "applicabilit"" notation on Figure 2 should be changed..to read "5 EFPY" in lieu of "2 EFPY after 6/79."

j 7

fy k/

,- /

tce, t S Nooi n, Chief Engineering Branch Division of Operating Reactors

Contact:

K. G. Hoge X27367 cc:

D. Eisenhut L. Shao G. Mazetis R. Reid S. Israel' D. Dilanni W. Hazelton K. Hoge R. Vollmer 80102304tv0 g