L

^

DEC 2 9 TM i

'NEMORANDUM FOR: Jack E. Rosenthal, Chief AEOD/T927 Reactor Operations Analysis Branch Division of Safety Programs Office for Analysis and Evaluation of Operational Data l'

THRU:

Matthew Chiramal, Chief L

Engineering Section Reactor Operations Analysis Branch Division of Safety Progrems Office for Analysis and Evaluation of Operational Data L

FROM:

Chuck Hsu,_ Mechanical Engineer Engineering Section Reactor Operations Analysis Branch Division of Safety Programs Office for Analysis and Evaluation of Operational Data SUBJEC;:

FOLLOW-UP ON STEAM BINDING 0F AFW PUMPS Enclosed is'a Technical Review report on retrospective study of operating experiences involving steam binding of AFW pumps. The study was initiated because of a concern whether licensee actions to prevent steam binding of AFW pumps were adequate following the issuance of Bulletin 85-01. This report indicates that none of the backleakage events that occurred after the issuance

'of the bulletin have resulted in the steam binding of an AFW pump.

It would seem appropriate to conclude that the actions taken by the licensees have been effective in monitoring and correcting the backleakages early enough to prevent any subsequent steam binding of the AFW pumps.

Therefore, no further AE0D action is needed.

Inf f

Chuck Hsu, Mechanical Engineer Engineering Section Reactor Operations Analysis Branch Division of Safety Programs Office for Analysis and Evaluation of Operational Data

Enclosure:

As stated Distribution:

PDR Central!ffiel, ROAB R/F CHeltemes DSP R/F TCintula GLanik EJordan KBlack MWilliams TNovak CHaughney HFaulkner MTaylor BBrady LSpessard VBenaroya 2

f)

//~/

ROAB:DSP:AE0D ROAB:DSP:AEOD RCAB:DSP:AE0D CHsu:as c H.

MChiramal k JRosenthal MO3

,e,!

11/IS/89 11/q /89 ILhffE9

'l A

9001100075 891229 PDR ORG NEXD r

r e