Special Rept:On 891121,fire Dampers Inoperable Longer than Seven Days.Caused by Deviations from Mfg Approved Construction Installation Details.Estimated Completion Date for Restoration of All Dampers Set for 901231
ML20005E304
Person / Time
Site: Trojan File:Portland General Electric icon.png
Issue date: 12/21/1989
From: Yundt C
PORTLAND GENERAL ELECTRIC CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
CPY-348-89, NUDOCS 9001050034
Download: ML20005E304 (3)


Text

y e

m

  • l h

I'

' Phrtland General Electric Company.

December 21, 1989-Trojan Nuclear Plant -

CPY-348 ' 71760 Columbia River liwy:

1

' Rainier, Oregon 97048 (503) 556-3713

'U. S. Nuclear Regulatory Commission Document Control Desk ~

Washington, DC 20555 Gentlemen:

Speefal Report Limiting Condition for Operation (LCO) 3.7.9 " Penetration Fire Barriers" of the Trojan Technical Specifications (TTS) requires submittal.of a Special Report if a

three hour fire barrier is nonfunctional for greater than seven days.

As the result of an ongoing program to identify deviations from the fire dampers manufacturers' approved' construction installation details, many fire dampers at-the Plant can not be c'onfirmed to meet all design specifications and are thus effectively inoperable.

The deviations can be placed into the following-

?

categories:

Deviation Possible Effect 1.

Inadequate or Unknown mounting Damper frame may bind.

Opening larger sleeve to.strveture clearance than acceptable gap during fire and therefore not meeting UL 555 criteria.

2.

No approved breakaway connection Damper may open larger than acceptable-

'where required.

gap during fire due to failure of attached duct work.

Same effect as No. 1.

3.

Insufficient or missing Caps may be present between the fire retaining angles damper assemble and the structure failing U1 criteria.

The fire damper assembly may fall out of the wall.

4; Missing fire damper sleeve or Missing sleeve may cause damper to missing UL label.

fall out of wall. Missing UL label questions listing of damper.

The following fire dampers were determined to be inoperable under this review program on or after November 21, 1989, and have been inoperable longer than seven days.

Due to the large number of dampers discovered to be inoperable under this program, the complexity of the repairs, availability of repair and replacement parts, and man power scheduling the estimated completion date for restoring all of the dampers to an operabic status is December 31, 1990. The compensatory measures of Technical Specification 3.7.9 (checking local smoke detectors and establishing an hourly fire patrol) were established immediately for each damper, as required.

192 Qf105003499122, s

ADOCK 050oo344 PDC

f-X y:m "

c d

r s-y<C U. S. Nuclear Regulatory.. Commission-

-Page 7 of 3-s.

The specific fire dampers of concern aret 1.-

Fire Damper 49 located in the East Battery room.(Room 40) on the east wall.

2.

Fire Damper 49A-located in the East Battery room (Room 40) on the east wall.

Fire Damper 50 located in the West Battery room (Room 39) on the east wall.

3.

4 Fire Damper 52 located in turbine driven Auxiliary Feed Water (AFW) Pump room (Room 91) on the south wall.

5.-

Fire; Damper 57 located in the West Emergency Diesel Generator (EDG) room (Room 85) on the north wall, 6.

. Fire Damper ~58 located in the West'EDG room (Room 85) on the north wall.

7.

Fire Damper 59 located in the East EDG room (Room 86) on the north wall.

8.-

, Fire Damper 60 located in the East EDG' room (Room 86) on the north wall.

9.

Fire Damper 61 located in the East EDG room (Room 86) on the west wall.

~

10.

Fire Damper 62 located in the East EDG room (Room 86) on the east vall.

11.

-Fire Damper 63 located-in the east EDG room (Room 86) on the east wall.

12.

-Fire Damper 90 located in the diesel-driven AFW Pump room (Room 90) on the east wall.

13.

Fire Damper 90A located in the diesel-driven AFW Pump room (Room 90) on the east wall.

14.

Fire Damper 94 located in the Electrical Switchgear room (Room 38) on the i

south wall.

15.

Fire Damper 95 located in the Electrical Switchgear room (Room 38) on the south wall.

16.

Fire Damper 96 located in the 61 Foot elevation Mechanical room (Room 34) on the north wall.

17.

Fire Damper 98 located in the Electrical Switchgear room (Room 38) on the south wall.

18.

. Fire Damper 99 located in the Electrical Switchgear room (Room 38) on the south wall.

19.

Fire Damper 104 located in the 77 Foot elevation Mechanical room (Room 46) on the north wall, i

,. g,'.

E' I

s U$S.NuclearRegulatoryCommission

.Page-3 of 3 20.

Fire Damper 137A located in the Electrical Switchgear room (Room 38) on the-east wall.

21.

Fire Damper 137B located in the Electrical Switchgear room (Room 38) on the east wall.

22.

- Fire Damper 139 located in the diesel driven AW Pump room (Room 90) on the west wall.

Sincerely, C. P.

undt General Manager Trojan Nuclear Plant CPY/J L/UWS/RQR/ S TRB c: