ML20005D876

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 890909-1020.Violation Noted:Failure to Follow Existing Procedures for Maint & Mods of Plant Configurations Involving Auxiliary Fuel Handling Bridge
ML20005D876
Person / Time
Site: Rancho Seco
Issue date: 12/07/1989
From: Chaffee A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To:
Shared Package
ML20005D874 List:
References
50-312-89-15, NUDOCS 9001020131
Download: ML20005D876 (2)


Text

.

APPENDIX A NOTICE OF VIOLATION Rancho Seco Nuclear Generating Station Docket No. 50-312 Sacramento Municipal Utility District License No. DPR-54 14440 Twin Cities Road Herald, California 95638-9799 During an NRC inspection conducted on September 9 through October 20, 1989, violations of NRC requirements were identified.

In accordance with the

" General Statement of Policy and Procedure for NRC Enforcement Actions,"

10 CFR Part 2, Appendix C, the violations are listed below:

A.

10 CFR Part 50.59 and Rancho Seco Administrative Procedure RSAP-0303, Plant Modifications, require in part that a written safety evaluation by performed for changes to a facility as described in the safety analysis report.

Contrary to the above, the auxiliary fuel handling bridge which is described in the licensee's safety analysis report, was dismantled and-removed from the reactor building in October,1989, under Work Request l

No. 01650150-0.

This facility change was not controlled under RSAP-0303 and, as a result, no written safety evaluation was performed.

This is a Severity Level IV violation (Supplement 1).

B.

Technical Sp"ecification 6.8.1 requires in part that procedures referenced in Appendix A" of Safety Guide 33, November 1972, be established and t

implemented.

Safety Guide 33, Appendix "A", para raph I.5, references procedures for the control of maintenance and modi ication work.

Rancho Seco Administrative Procedure, RSAP-0803, R.5, Paragraph 5.5.14, states, in part:

t l

"The work request shall be changed to reflect the work required to be performed..."

Contrary to the above, in October,1989, Work Request No. #01650150-0 was not changed to temporarily relocate the auxiliary fuel handling bridge from the fuel transfer canal to the 60 ft level ~of the reactor building.

The work request only directed the equipment to be dismantled and removed from the reactor building.

The increase in the scope of the work activity required to be performed was not prescribed by a change to the work request.

This is a Severity Level IV violation (Supplement 1).

N$$d$$$$8h PDC

.i f.

-2 Pursuant to the arovisions of 10 CFR 2.201, the Sacramento Municipal Utility District is heresy required to submit a written statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN:

Document Control Desk, Washington, DC 20555 with a copy to the NRC Resident Inspector, Anthony D'Angelo, within 30 days of the date of the letter transmitting this Notice.

This reply should be clearly marked as a " Reply to a Notice of Violation" and should include for each violation:

(1) the reason for the violation if admitted, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be~ taken to avoid further violations, and (4) the date when full compliance will be achieved.

If an adequate reply is.not received within the time specified in this Notice, an order may be issued to show cause why the license should not be modified, suspended, or revoked or why such other action as may be proper should not be taken.

Consideration may be given to extending the response time for good cause shown.

FOR THE NUCLEAR REGULATORY COMMISSION ff t

A. E. Chaffee, Deputy Director Division of Reactor Safety and Projects Dated at Walnut Creek, California this day of 0,,A. 1989

-