ML20005A765

From kanterella
Jump to navigation Jump to search
Submits Info in Response to NRC 810626 Request Re Fire Protection Review.Cooling Air Supply for Redundant Panels Involved in Safe Shutdown Will Be Provided from Overhead Air Conditioning Ducts
ML20005A765
Person / Time
Site: Fermi 
Issue date: 06/29/1981
From: Colbert W
DETROIT EDISON CO.
To: Kintner L
Office of Nuclear Reactor Regulation
References
EF2-53-897, NUDOCS 8107010214
Download: ML20005A765 (2)


Text

.

m D/ f>g.

G prt

~

0 $,i h'-

9 JUN 001981m E 20co secena Avenue

_....S C n Ssi#ra" "

s "wp fg% /\\Y June 29, 1981 W'I'N EF2 -53,897 Mr. L.

L. Kintner Division of Project Management Office of Nuclear Reactor Regulation U.

S.

Nuclear Regulatory Commission Washington, D. C.

20555

Dear Mr. Kintner:

Reference:

Enrico Fermi' Atomic Power Plant, Unit 2 NRC Docket No. 50-341

Subject:

Fire Protection Review In response to additional verbal requests by Victor Benaroya on June 26, 1981, the following information is provided:

1 The plastic materials on control panel surfaces are:

1.1 CMC switch is made of Lexan, Valox and Zytel.

There is 1 small Buna-N gasket between the control panel surface and the face of the switch.

1.2 Pushbutton front lens is Mil. Spec P5425 finish A or LP-391 Type 2 Grade A.

Diffuser is acrylic Mil. Spec P-21105B.

1.3 Mimic lines are "GRAVOPLY" modified acrylic resin XT 375 manufactured by American Cyanamid,.062 inches thick.

2.

The video tape taken of the fire test, which was conducted to show the effect of an external exposure fire on the panel mounted components, is hand-carried by L.

E.

Schuerman and will be given to you on June 30, 1981.

3o0}

s!D

/

8107010214 810629 PDR ADOCK 05000341 F

PDR

' as Mr. L. L. Kintner June 29, 1981 EF2 - 53,897 Page 2 3.

The cooling air supply for three pair of redundant panels involved in safe shutdown (H11-P601 & P602; P808 & P817; P809 & P810) will be provided from the overhead air conditioning ducts and therefore will not be affected by a control room exposure fure.

4.-

The. fire fighting instructions require dry chemical or CO2 use on electrical panels.

The control room panels are not waterproof design, but the small gasket

.on the CMC switch and the close fit of the mounting of the pushbuttons is expected to minimize the effects of accidental splashing of small amounts of water.

Sincerely, L

W.

F.

Colbert 4-Technical Director Fermi 2 Project 1

WFC/EL:jl 4

cc:

Mr. B.

Little l

i i

-