ML20004F097

From kanterella
Jump to navigation Jump to search
Forwards LERs 81-014/03L-0 & 81-015/03L-0
Date released: 01/18/2020 Download: ML20004F097


LER 81-015/03L-0:on 810506,hydrogen Recombiner 2A Oxygen Concentration Increased Above Tech Spec Level w/4.3% Hydrogen Concentration.Cause Not Stated.Oxygen Concentration Reduced & Recombiner Returned to Svc
ML20004F117
Person / Time
Site: Farley 
Issue date: 06/09/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20004F117 (1)
LER 81-014/03L-0:on 810506,sequencer B2J Failed to Load Shed River Water Pump 3 During Loss of Sys Pressure Test.Caused by Malfunction of Relay Due to Dirty Contacts.Contacts Cleaned & Adjusted & Sequencer Returned to Svc on 810507
ML20004F106
Person / Time
Site: Farley 
Issue date: 06/09/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20004F106 (1)
Forwards LERs 81-014/03L-0 & 81-015/03L-0
ML20004F096
Person / Time
Site: Farley 
Issue date: 06/09/1981
From: Clayton F
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20004F096 (1)