Reponds to IE Bulletin 81-03, Flow Blockage of Cooling Water to Safety Sys Components by Corbicula Sp (Asiatic Clam) & Mytilus Sp (Mussel). Fire Protection Sys Is Not Susceptible to Clam Infiltration.No Mussels Present
ML20004F003
Person / Time
Site: Hatch  
Issue date: 05/22/1981
From: Beckham J
GEORGIA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-81-03, IEB-81-3, NUDOCS 8106160367
Download: ML20004F003 (2)


Text

Grorg'a P wer Cor*cany 0

j 333 P ec~cnt Annua Ara-ta Georgia 30308 Terencre 404 525 6526 e,.:,

Vamrg accress Post cmce Sex 4545 arranta Georga 30302 1 gl GeorgiaPower M Y 22 r

7 p,

y Power Generation Department

, fge rA United States Nuclear Regulatory Commission 9

l3 JUM 16 Ny Office of Inspection and Enforcement

REFERENCE:

50-321/50-3Mk,,s,,ew*g' 2)

RII: JP0 Region II - Suite 3100 co'*

101 Marietta Street, NW

/

Atlanta, Georgia 30302 I&E Bulletin 8143 4/

/

NS A A

ATTENTICN: Mr. James P. O'Reilly N 'df Gentlemen:

Georgia Power Company hereby submits the following in response to I&E Sulletin 81-03, " Flow Slockage of Cooling Water To Safety System Components By Corbicula Sp. (Asiatic Clam) and Mytilus Sp. (Mussel)":

Corbicula Sp. (Asiatic clam) has been found previously in the Altsmaha River.

River water is used at Plant Edwin I. Hatch for service water and circulating water systems.

The fire protection system uses water from a deep well and therefore is not susceptible to clam infiltration.

The Mytilus Sp. (Mussel) is a salt water species and is not present in the Altamaha River in the Plant Hatch vicinity.

Upon receipt of the bulletin a visual inspection was performed for piping and systems which use service or circulating water.

This inspection included the following:

"O" Condenser Water Box on Unit 2, all condenser water boxes on Unit 1, Main Turbine Oil Coolers en Unit 1, Main Generator Hydrogen Coolers on Unit 1, Alterex Cooler on Unit 1, Stator Water Coolers on Unit 1, E.H.C. Coolers on Unit 1, RHR Area Room Cooler on Unit 1, HPCI Area Room Cooler on Ut.it 1, and Drywell Fans Chiller Cooling Coils on Unit 1.

This insoection included the various size piping down to the tubes inside the aforementioned components.

No signs of clams or clam shells were observed in any of those systems inspected to date.

We are still awaiting inspection of a RHR heat exchanger and some service water piping at the intake structure.

We do not expect to find any evidence of clams in these systems.

In the event that clams are detected, NRC will be notified.

Adult clams, if present, would be stopped by screens at the intake structure.

Due to the small size of clam larvae, the cotential for intrusion is a constant possibility.

Larvae are controlled by chlorination of the service water and circulating water systems.

The service water systems usually attain about a 0.3 ppm chlorine residual.

Circulating water systems are presently chlorinated up to three times a day for thirty to forty minutes each time and usually attain a maximum recidual of 0.2 ppm chlorine.

'.EGtI s4 h

810616s367

s GeorgiaPower A United States POclear Regulatory Commission Office of Inspection and Enforcement Atlanta, Georgia 30302 May 22, 1981 Page Two Present detection methods are normal maintenance practices, including periodic dismantling and repairs of systems.

If any organisms or organic fculing are observed, appropriate actions will be taken.

The existing program appears to be effective in detecting any biological fouling and its use will be continued.

The environmental monitoring

program, as established under the Environmental Technical Specifications, recuires sampling for clams semiannually.

Tne Altamaha River in the vicinity of Plant Hatch was last sampled for clams on December 2, 1980. Clams were found to be present.

If you have any c;uestions in this regard, please contact my office.

J. T. Beckham Jr. states that he is Vice President of Gatorgia Power Company and is authorized to execute this oath on behalf of Georgia Power Company, and that to the best of his knowledge and belief the facts set forth in this letter are true.

^*

GEORGIA POWER COMPANY By:

3

-h y J. T. eecxnam, Jc Sworn to and subscribed before me this 22nd day of May,1981.

i p e S ot.

1983 f

Notary Puolic JAE/mb xc:

M. Fenry R. F. Rogers; III Director, Office of Inspection and Enforcement 1

f

__.