ML20004B177

From kanterella
Jump to navigation Jump to search
Forwards LER 81-017/99L-0
Date released: 01/18/2020 Download: ML20004B177


LER 81-017/99L-0:on 810424,during Mode 1 operation,30 Out of 32 Resistance Temp Detectors Did Not Meet Tech Spec Response Time Limit of 6-s.Caused by Inadequate Contact of Couplant Thermowells.Wells Cleaned & Visually Inspected
ML20004B185
Person / Time
Site: Arkansas Nuclear 
Issue date: 05/20/1981
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML20004B185 (1)
Forwards LER 81-017/99L-0
ML20004B176
Person / Time
Site: Arkansas Nuclear 
Issue date: 05/20/1981
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: MADSEN G L
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML20004B176 (1)