May 14, 1981 Docket No.50-35e Mr. Harold Denton, Director
' E Eo"w "
Office of Nuclear Reactor Regulation
<q
\\.
k U.S. Nuclear Regulatory Commission M
Washington, D.C.
20555 RE:
WM. H. ZIMMER NUCLEAR POWER STATION -
UNIT 1 - AMENDMENT 119 - SUBMITTAL OF PIVISION 18 TO THE FIRE PROTECTION EVALUATION REPORT
Dear Mr. Denton:
The Cincinnati Gas & Electric Company on behalf of itself and as agent for Columbus and Southern Ohio Electric Company and The Dayton Power and Light Company hereby submits forty (40) copies of Revision 18 to the Fire Protection Evaluation Report for the Wm. H. Zimmer Nuclear Power Station - Unit 1 (ZPS-1).
Very truly yours, THE CINCINNATI GAS & EI.ECTRIC COMPANY M
N.-
E. A. BORGMANN EAB: dew cc: Charles Bechhoefer State of Ohio
)
M. Stanley Livingston County of Hamilton)
Frank F. Hooper Troy B. Conner, Jr.
Sworn to and subscribed before me this James P. Fenstermaker
/#
day of May
, 1981, Steven G. Smith William J. Moran J. Robert Newlin William G. Porter, Jr.
f c.A,m u I
.e James D. Flynn Nrt}ry Public F. T. Daniels W. Peter Heile MARGARET L. HUBER James H. Feldman, Jr.
Netary Putlic. :ste Of Ohio John D. Woliver My Commissma Expires A.g. 13.1983 Mary Reder David K. Martin George E. Pattison Andrew B. Dennison 81051sogn f
i
- s...
6
~ ZPS-REVISION 18' t
MAY-1981 '
WM. H. ZIMMER POWER STATION.
' INSTRUCTIONS FOR UPDATING YOUR FIRE PROTECTION EVALUATION REPORT To update your copy of the ZPS-1 Fire Protection Evaluation Report, j
remove and destroy the follawing pages and. insert pages and figures-as indicated.
REMOVE INSERT Page Q4-1 Page Q4-l' Figure Q4-1
-Figure Q4-1 O'
LO P00R 011GINAL 1
L.
ZPS-1.
ISI N 18 i
v}
QUESTION 4 (OUTSIDE AUXILIARY BUILDING) f r
"A fire in the main auxiliary transformer or the reserve auxiliary.
transformer outside at the southeast-corner of the ' auxiliary building i
would create excessive smoke. Describe how the smoke from this postulated fire, or any other fire on the south or' east side of the I
building, will;be prevented from entering the air intake plehums
~
(for the diesel-generator rooms or other areas) which are located i
on the south wall of *.he auxiliary building directly above the l
transformers, and thereby activating the ionization detectors which will discharge CO into the diesel-generator rooms."
2 r
i dESPONSE Smoke from an outside s rce, such as a transformer fire, could possibly I
enter the air intake louvers located in the auxiliary building wall at
.i column row 15.
The ventilation filters will remove 50% of all particles in the 3 micron range and 100% of particles in the 10-micron range; therefon, the major amount of smoke particles would be removed by the ventilation system filters. Additional filtration is available when the evaporative cooling units are operating in the summer, j
The diesel-generator rooms are normally ventilated and maintained at a slight positive pressure by the turbine building ventilation system.
The diesel-generator air intake fr operate only when a diesel generator t
is operating. The CO systems in t. diesel-generator rooms are actuated r
2 by fixed temperature detectors, thus the presence of smoke in the diesel-generator rooms will not cause an inadvertent discharge of the C0 7
systems.
The actuation of the heat detectors in the diesel-generator rooms init-7 iates an alarm both Iccally and in the' control roon prior to actuation of the CO fire pr te:ti n system.
2 l 17 At the south end of the auxiliary building, a sheet metal enclosure is provided. Its main purpose is to provide air from the northerly direction and 1%it DEG fumes and smoke from entering the south minimum outside-air 18 intake of the control room HVAC snd Division 2 diesel ventilation system.
I I
Since Division 1 and Division 2 diesels provide redundant power supplies to saf-Nt down the plant, the ventilation and combustion air i
intakr
- a Division 2 diesel is routed to the auxiliary building roof l
~
(elevs.<'n S' f t 7 in.) to provide a separate and diverse intake for 15 i
.ompared to Division 1 (and 3) intakes. The separate and
_[
this c > o diverse.
takes, therefore, provide protection from concentrated combustion products produced by a fire from the main transformer located
(
south of the diesel building at grade (elevatior 520 ft 0 in.).
[
i J
{
Q4-1
?
~
REVISION 18
{
MAY 1981 TURBINE O
DIESEL BUILDINo x
i GENERATOR j
(DIV. 2 )
REACTOR l
AND BUILDING 1
AUXILIARY BUILDING AUXILIARY AIR-INTAKE BUILDING
/
ENCLOSURE P'
DIESEL GENERATOR DIV.2) m,/ AIR INTAKE OPENIN K. -
4 ROOF
',/
s.
[
,/
~
p p
,-lOI"
, f'
/
,s c
',/
. j:j-.j:;
N,,
4 g
i
- ,r' I
f
)
/
l y-
- H.V.AC.
1.
AIR-INTAKE LOUVERS
% DIESEL
/
GENERATOR (DIVh. I 8 3) l
/
AIR-INTAKE LOUVERS Noiesc' eesea*Toa coiv. 2)
O
/
/'
AIR-INTAKE LOUVERS (SEALED CLOSED)
/
DIESEL GENERATOR
/
BUILDING l
/
I DIESEL GENERATOR y
EXHAUSTS AUXILIARY
\\
MAIN POWER RESERVE AUXILIARY l
TRANSFORMER TRANSFORMER TRANSFORMER
!SOMETRIC i
h[g
[ll llll MI'RNbNIIIIIIIIIIIllI i
ENCLOSUREm %f$ DlWT 018.INTAKg,OPNG
/
4 l:8 VENTILATION EQUIPMENT ROOM EL. 567 '- 5" SWITCHGEAR CONTROL
(
n f"5 ROOM ROOM EL. 54 6'-O"
.--a
[
- - EL. 520'-0" f
\\
WM. H. ZIMMER NUCLEAR POWER STATION. UNIT 1 0
r>ac eao'cor'oa ateoar
DIESEL lM l
GENERATOR FIGURE Q4-1 ROOM SECTION ISOMETRIC VIEW 0F DIVISION 2 DIESEL AIR INTAKE c
t