ML20003H270

From kanterella
Jump to navigation Jump to search
Forwards LER 81-035/03L-0
Date released: 01/17/2020 Download: ML20003H270


LER 81-035/03L-0:on 810403,auxiliary Feedwater Pump 1A-S Tripped on Electrical Overspeed After Inadvertent Pump Start.Caused by Locking Nut on Control Circuit Trimpot Vibrating Loose & Allowing Setpoint to Drift
ML20003H273
Person / Time
Site: Sequoyah 
Issue date: 04/30/1981
From: Harding M, Wilkey A
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003H273 (1)
Forwards LER 81-035/03L-0
ML20003H269
Person / Time
Site: Sequoyah 
Issue date: 04/30/1981
From: Green H
TENNESSEE VALLEY AUTHORITY
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003H269 (1)