Submits Supplemental Response to IE Bulletin 80-06, Engineered Safety Feature (ESF) Reset Controls. Valve Designation for 800625 Response 1,Item B Should Be CV-4190 Instead of CV-4090.Approx 150 Manhours Expended on Review
ML20003D137
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 03/11/1981
From: Withrow G
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
IEB-80-06, IEB-80-6, NUDOCS 8103190351
Download: ML20003D137 (2)


Text

,

/ ! L,-

@ Consumers Power Company General Offices: 212 Vuest Michienn Avenue, Jacuson, Michagen 49201 + (517) 7884650 March 11, 1981 Mr Ja=es G Eeppler Office of Inspection and Enforcement h

\\

Regicn III

[

I/bj h,2 US Nuclear Eegulatcrv Cc==ission "y a 799 Ecosevelt Road g] Es, 2 O I90I b 4 Glen Ellyn, IL 60137

,oes DCCC:' 50-155 - LICE'!SE DPE ki Ap 02., i

.n.aG :t.a.:s r,.

m... - c,urr.r.:

a.x_,

g r-v FISPCNSE TO IE EULL2"IN NO S0 O ENGIM.:.:tED SA::.af FIA"UEE (ESF)

FISET CONTECLS Cons =ers Pcver Cc=pany letter dated June 25, 1930 provided c"

  • ** *
  • al re-spense to IE Eulletin No BC-C6 dated March 13, 1980. That respense provided the results of cur deccentation review and indicated that verification tests vould be perfor=ed during the next refueling cutage (ie, 1930-51 Eefueling Cutage).

The verification tests have been perfomed and dec=ented.

"he test results verified that upcn the reset of an ESF actuaticn signal, all safety related equip =ent re ains in its energency rede, except the containment aut o-

=atic isclatien valves and the off-gas isclaticn valve as described in cur initial respense.

Cn February 2, 1961, a discussion with Mr W Paulsen of the NRC - NER cecurred in which certain clari'ications to our initial response vere made. Per Mr W Faulson's requesu, the following NEC questions and cur responses to ther are provided:

1) NEC Question: Frovide a list of equipment centrclied by the

" initiating moniter" rentioned in cur response to ite= 1.

Response: Major Equip =ent - SV LS57 for off-gas isolation valve CV-h015 Associated Equipment - Ala= for off-gas ti=er

- Drain line valves in off-gss isolation syster SV L868 for CV h030 SV LB72 for CV LO35 8103190 %

1 3 1981 Sv-aL27 (Drain to turbine s=p)

Sv ug36 cerein to radveste s=r) g

r =

Mr' James G Keppler 2

Rig' Rock Point Plant March'll,.1961 2)- NRC' Question:

Do the - contain=ent. automatic ventilation isolation /

vreuun relief va) es anteratically reclose following a vacuu: relief function?

Respense: The valves vill auto =atically open and stay open until the vacuu= signal goes below setpoint (1 psig negative - FHSR section 3.5.2.3).

During pcver operation or refueling operation the valves vill auto =atically close on reactor scra signals or on a high radiation signal from either of the two ares monitors on the refueling deck.

During shutdown

. (mode -switch in shutdown) the valves vill aute ati-cally' close on reactor lov level or contain=ent high pressure cn on either of the two high radiation signals from the refueling deck-area conitors.

. An error 'has been identified in our response dated-June 25, 1980.

It involves

~

the valve designation for response 1, -ite: h which should be CV L190 instead of

_CV h090.

Nor ally 1the level of effort is_ requested by the NBC in responding to IE Rulletins;

~I therefore, duef to, the. level of effort an esti= ate of manpower expenditure is pro-

~

a vided,leven. though1not-specifically requested. - Reviews, testing and preparatien of the responses -to_ this bulletin involved approximately 150 =an-hours.

l. W Y A W

- Gregory C Withrov_'

--Senior Licensing' Engineer -

CC -Director, Office of Nuclear _ Reactor Regulation Director, Office of Inspection and Enforcement-

~

NRC Resident Inspector:- Big Rock Point h

V v

~

a IL N

-_,____2'.

2 a

m m

. r'.

n m.

m....n.

aa a

m.- m. m.

.a A...mu

{.

[.<

l CONSU!ERS POWER COMPANY Big Rock Point Plant IE Bulletin No 80-06 Docket No 50-155 License No DPR-6 At the request of the Commission and pursuant to the Atomic Energy Act of 195k, and the Energy Reorganization Act of 197h, as amended and the Commission's Rules and Regulations thereunder, Consumers Power Company submits a supplemental response to IE Bulletin No 80-06, dated March 13, 1980, entitled,

" Engineered Safety Feature (ESP) Reset Controls".

Consumers Power Company's supplemental response is dated March 11, 1981.

CONSUMERS POWER COMPANY p

\\

k'g J

By

~

R B DeWitt, Vice President Nuclear Operations Sworn and subscribed to before.me this lith day 'of March 1981.