ML20003B755

From kanterella
Jump to navigation Jump to search
Forwards LER 81-006/03L-0
Date released: 01/17/2020 Download: ML20003B755


LER 81-006/03L-0:on 810113 Diesel Generator 12 Switchgear Would Not Close in on 21 4-kV Bus Per Tech Spec.Caused by High Resistance at Secondary Disconnect.Continuity of Closing Circuit Interlocks Verified & Switchgear Tested
ML20003B762
Person / Time
Site: Calvert Cliffs 
Issue date: 02/12/1981
From: Lagiewski J, Rizzo P
BALTIMORE GAS & ELECTRIC CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML20003B762 (2)
Forwards LER 81-006/03L-0
ML20003B754
Person / Time
Site: Calvert Cliffs 
Issue date: 02/12/1981
From: Russell L
BALTIMORE GAS & ELECTRIC CO.
To: GRIER B H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML20003B754 (1)