ML20003A634

From kanterella
Jump to navigation Jump to search
Forwards Updated LER 80-027/03X-1
Date released: 01/17/2020 Download: ML20003A634


Updated LER 80-027/03X-1:on 800714,RHR Pump 3D Motor Tripped on Instantaneous Overcurrent.Caused by Dc Offset Due to High Saturation of CT Increasing Current Monitored.Motor Meggered,Potted & Bridged.Rhr Relay Settings Revised
ML20003A635
Person / Time
Site: Browns Ferry 
Issue date: 01/29/1981
From:
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003A635 (2)
Forwards Updated LER 80-027/03X-1
ML20003A633
Person / Time
Site: Browns Ferry 
Issue date: 01/29/1981
From: Green H
TENNESSEE VALLEY AUTHORITY
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003A633 (1)