Clarifies 800711 & 1202 Responses to IE Bulletin 80-10 Re Contamination of Nonradioactive Sys & Resulting Potential for Release.All Floor Drains W/Potential for Release to Environ Have Been Plugged
ML20002D645
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 12/19/1980
From: Hoffman D
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
IEB-80-10, NUDOCS 8101210609
Download: ML20002D645 (2)


Text

TW c

4 CORSumBIS POVVer COmpHuy General Offices: 212 West M6chigen Avenue, Jackson, M6chigen 49201 *(517) 788-0550 December 19, 1980 Fr James G Keppler Office of Inspection and Enforcement Region III US ::uelear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 DOCKET 50-155 - LICE:iSE DPR BIG ROCK POII;T PLA'iT - SUFFLDINTAL RESFO:iSE TO IE EULLETIN NO 80 CC:;TA"JNATIO:I 0F HCNEADICACTIVE SYSTE'S A?ID RESULTING POTENTIAL FOR UN:C::ITORED, UNCONTROLLED RELEASE OF RADI0 ACTIVITY TO ENVIRCN GNT Consumers Power Ccmpany has previously responded to IE Bulletin 80-10 on July 11, 1980 and December 2, 1980 (supplemental response).

Our supplemental response was to provide additional information requested by NRC Region III inspectors during the November 3-6, 1980 inspection.

IE Inspection Report No 50-155/80-16, dated December 3,1980, has been recently recieved and upon our review indicates that our previous responses need further amplification.

Therefore, in respense to the inspector's request and our commitment that certain responses be formally docketed, the following information is provided:

(Note:

Responses in addition to those previously given in our letter dated December 2, 1980 are identified by lines in the right margin.)

1.

All floor drains having a potential for radiological release to the environment from plant equipment were identified and those that drained to the environment (ie, Lake Michigan which is immediately adjacent to the plant) vere plugged.

2.

The sluicing of spent demineralizer resins to a shipping cask requires the use of a procedure which requires that yard drains in the vicinity of the pumping operation be plugged and sealed before the pumping operation commences.

3 The potential for contamination of breathing air supply systems vill be addressed by performing a routine sampling of the such air supply lines, which is scheduled to commence on January 1, 1981. Additionally, to assure clean breathing air for plant DEC 2 2 son 8101010 %

Mr Jam;s G Kspplcr 2

Big Rock Point December 19, 1980 8

vorkmen, it is our practice to use an bEA manifold for all breathing air purposes supplied by plant air systems. The manifold contains a pressure regulator, a particulate and carbon filter, and connections for approximately four workmen.

4.

The plant heating boiler system is no longer used for reactor core physics test (moderater temperature coefficient test).

Separation of these two systems (shutdown heat exchangers) is maintained by a locked valve and procedural controls.

Demineralized water is the primary source of make-up water supply to the plant heating boiler. This source is sampled and analyzed for radioactivity on a routine basis. Therefore, there is no need to sample the plant heating system directly.

5 The influent to the sanitary waste system is from the usual sanitary receptacleslocated in the office section of the plant and from the plant heating boiler blowdown tank.

The effluent from the collection system is pumped to an on-site leaching field. Therefore, there is no need to sample the sanitary vaste system directly.

6.

Potable water is supplied from an on-site deep vell pump and a 670 gallon domestic water accumulator storage tank.

Review of this system also indicates that ss=pling and analysis for radio-activity is unnecessary.

It is our belief that the concerns of IE Bulletin No 80-10 and the NRC Region III inspectors have been resolved by our previous responses, the infor-mation provided on-site and the information provided herein; therefore, no additional actions are planned pursuant to this bulletin.

(d

)

David P Hoffman Nuclear Licensing Adminstrator CC Director, Office of Nuclear Reactor Regulation Director, Office of, Inspection and Enforcement NRC Resident Inspector - Big Rock Point i