Forwards Request for Change 20 to Tech Specs of License DPR-6,allowing Use of 1-Y Bus as Normal Supply of Power to Control Rod Drive Position Indicating Sys & Associated Interlocks & Relays
ML20002C986
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 02/27/1970
From: Haueter R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Morris P, Skovholt D
US ATOMIC ENERGY COMMISSION (AEC)
References
NUDOCS 8101150660
Download: ML20002C986 (4)


Text

.

MU n

Consumers f Q 't, QF power 4.,Y g C0mpany ff l

-f q

Qkg '2,\\go y

gd

-t w

y on.c.: m.E west dy gan Avenue.Jacmn, McNgan 49201. Area Code

~

t o ner.:

517 788-OSSO j.;

+

h 'fd / y \\ [

D February 27, 1970 u

sM w

1 M'lM' Regulatory File Cy.

Dr. P. A. Morris, Director Division of Reactor Licensing Re: Big Rock Point United States Atomic Energy Commission DPR-6 Washington, DC 20545 Docket 50-155

Dear Dr. Morris:

Attention:

Mr. D. J. Skovholt Transmitted herewith are three (3) executed and thirty-seven (37) confomed copies of a Request for a Change to the Technical Speci-fications of License DPR-6, Docket No 50-155, issued to Consumers Power Company on May 1,1964, for the Big Rock Point Nuclear Plant.

This proposed change (No 20) will enable the Big Rock Point Plant to utilize the 1-Y bus, fed from a 460/120 V a-c station power source, as the normal supply of power to the control rod drive position indicating system and associated interlocks and relays. The 125 V d-c operated motor generator set (formerly used as the normal power source) will be used for a standby source of power. Upon loss of power to the 1-Y bus, a throwover device to the motor generator set would operate automatically furnishing a backup power supply for the control rod position indicating system.

This new " normal power supply" vill provide for a more con-sistent power source, a reduction in routine maintenance time and an improved system reliability.

We would like to make this change during our present refueling outage (February-March 1970). Therefore, we vould appreciate an expedi-tious handling of this Request for a Technical Specifications Change so that we might receive approval before March 27, 1970.

i Yours very truly,

(

ERC/ map Robert L. Haueter l

Electric Production l

CC: GFiorelli Superintendent - Nuclear EJBrunner

/n

~ ~:

i r=

~ _ _ _ _ _

i I

)

CONSUbERS POWER C0b'PA?H i

Docket No 50-155 a

l Request for Change to the Technical Specifications Licence No DPR-6 t

5 I

i 1

l l

For the reasons hereinafter set forth, it is requested that l

i the Technical Specifications of License DPR-6, Docket 50-155, issued to Consumers Power Company on May 1,1964, for the Big Rock Point Plant be i

j changed as follows:

f I.

Section 4 In Section 4.2.l(a), second paragraph, line 8, change to read:

"The fourth bus is supp'ied from a different 480 volt system I

through a 480/120 volt (.-c transformer and power panel, which supp' tes power to the contro'. rod position indi-cating system. Standby power shall be supplied from the 125 volt d-c system using a motor generator set.... "

o t

II.

Discussion

(

The present 125 volt d-c operated motor generator unit was t

installed a number of years ago to supply 120 volt a-c power for the j

control rod drive position indicating system, associated interlocks and relays for the reactar crane. This unit has not performed to our satis-i faction since initial installation due to the following considerations:

1.

Poor voltage regulation re' alting in voltage swings in the system, complicated further by the trenthly overcharge placed on the battery.

2.

Dccessive maintenance to the motor generator unit, espe-cially due to heavy wear on slip rings and commutator.

3 High load requirements (30% of the normal load now supplied by the station d-c battery).

In the present system, the 1-Y bus furnishes only standby power to the 120 volt reactor protection system buses 1, 2 and 3 Power is supplied to the 1-Y bus from the 120 volt o-c instrument and control i

transfomer 2B, fed from a 480 volt a-c power source. The 1-Y bus has shown good reliability when needed during the past years and does not experience the voltage swings characteristic of the motor generator unit.

J

p!. * -

i

.(

p g-

.y 2

l' The proposed system, utilizing the 1-Y bus, would farnish

. power to the control. rod drive position indicating system, associated interlocks and relays. Reactor protection buses 1, 2 and 3 would not j

be affected by this change and would still have the 1-Y bus as backup if failure occurred to their respective power sources. The 125 volt d-c operated motor generator unit would be used as a standby source of power l

l-(automatically placed in service at full voltage in approximately fivc

}-

seconds) to the control rod drive position indicating system, associated I

interlocks and relays if power should fail tc. the 1-Y bus. This condi-i

{

tion is unlikely, however, because the emergency diesel generator pro-f vides a second source of power for instrument and control transformer 2B f

furnishing the 1-Y bus.

1 III. Conclusion We feel that the proposed change will provide for a more constant l

source of power, reduce future maintenance requirements and improve system f

f reliability.

l In our opinion, the proposed change does not involve an unreviewed or significant change in the hazards considerations described or implicit in the Final Hazards Summary Report.

CONSUMERS POWER COMPANY j

4 By Senior Vice President l

l Date: February 27, 1970 Sworn and subscribed to before me this 27th day of February 1970.

I

  • t ju !

a s mch I Notary Public, Jackson County, Michigan My Commission Expires January 15, 1972 i

~

u. - - _ _ _ _ _

~'

NO.s DATE CECIIVED TAT 3 CF DOCUMENT iI M M*N N"N RO Jackson, Michiama 49201 Omta.

> =T.

i.m.

m E=0.

ug%

E OTHEasl ORIS s Scs Le Pe'ter A. Morris 3 signes & 37 esaf'd 7 01 ACTION NECESSARY O

CoNCuRREuct O

DATE ANSWERED NO ACTION NECESSARY O COM M ENT O

ave POST OFFICE FILE CODE CLAS8t Fs N

REG.NO:

RECEtVED BY DATE DATE PtEFERR ED TO DEsc lFTION; (Must ble UncJassified) a,5 tL ras the followingt wf for action DI9fRIBUTION:

Regulatory file d

'F LACweuREs:

  1. DC PDR Request, notarised 2-27-70, for Ccarpliance(2)

Chang 3toTechSpecs(ProposedChange BOC (Rm P S06 Ai, h.20) g, ppge, g gg,p; Dubs /Levine (3 *i.. we4a3roo eare. 4)

,**=

DO NOT 1 VOE.

um_pocat=)

.g. gSDWLEDSE0

" ~ ~ -

_3 621 foe u.s. ATouic EncacY cOMMIS$10N MAIL CONTROL FORM roa M ^EC-smes t560)

..@ u S. eovsanisant en'avine omes, ses-ese J

PCCRCRl8lk1

..