Category:NOTICE OF VIOLATION OF A REGULATION
MONTHYEARML20207E0881999-02-26026 February 1999
[Table view]Notice of Violation from Insp on 990201-05.Violation Noted: on 990201,NRC Inspectors Identified That Area with Dose Rates Greater than 1000 M/H Not Provided with Locked or Continously Guarded Doors to Prevent Unauthorized Entry ML20198L7711998-12-24024 December 1998 Notice of Violation from Insp on 981207-11.Violation Noted: on 950630,licensee Made Change to Emergency Plan Without Commission Approval ML20196F1141998-12-0101 December 1998 Notice of Violation from Insp on 980920-1031.Violation Noted:From 980521 Through 981015,conditions Adverse to Quality Identified in Condition Rept 1998-0014 Not Promptly Corrected ML20248E7501998-05-28028 May 1998 Notice of Violation from Insp on 980405-0516.Violation Noted:On 980421,inspectors Found Back Doors on Diesel Generator Control Cabinet 1H22-p400 in Div 1 Standby Diesel Generator Room Standing Wide Open & Unattended ML20199L9411997-11-25025 November 1997 Notice of Violation from Insp on 970804-22.Violation Noted: on or About Period of 970117-29,approved FP Program as Described in UFSAR Was Not Fully Implemented.Emergency Light 1T92S222A Was Not Capable of Performing Function ML20198Q0291997-10-31031 October 1997 Notice of Violation from Insp on 970907-1018.Violation Noted:As of 971011,security Patrols Had Not Reported Dark Areas in Temporary Covered Maint Work Area in Protected Area ML20216J2081997-09-12012 September 1997 Notice of Violation from Insp on 970803-0906.Violation Noted:As of 970811,duplex Filter Selection Levers for HPCS & Div 1 Standby DGs Were in Both Position Such That Two Strainers/Filters Were Selected ML20210N0761997-08-19019 August 1997 Notice of Violation from Insp on 970622-0802.Violation Noted:On 970630,inspectors Identified Extension Ladder Supported on safety-related Cable Tray & No Engineering Evaluation Had Been Completed ML20216A8411997-08-0606 August 1997 Notice of Violation from Insp on 970714-18.Violation Noted: on 970717,compensatory Measures Not Implemented at Two Trailers within Protected Area Where Lighting Did Not Meet Required 0.2 Footcandles ML20151L9361997-08-0505 August 1997 Notice of Violation from Insp on 970714-17.Violation Noted:Individual Entered High Radiation Area W/O Monitoring Devices on 970123 & 0707 ML20148E2331997-05-29029 May 1997 Notice of Violation from Insp on 970310-27.Violation Noted: Licensee Had Not Updated FSAR to Assure That Info Included Contains Latest Matl Developed ML20148D4451997-05-27027 May 1997 Notice of Violation from Insp on 970323-0510.Violation Noted:On 970424,licensee Failed to Ensure That Qualified Individual Was Available to Respond for Er Organization Position of Offsite Emergency Coordinator ML20140E6351997-04-24024 April 1997 Notice of Violation from Insp on 970209-0322.Violation Noted:On 970227,design Engineer Failed to Implement Requirements of Procedure 01-S-03-10 ML20134P3581996-11-25025 November 1996 Notice of Violation from Insp on 960929-1109.Violation Noted:Five Required Channel Checks for Fuel Handling Area Pool Sweep Exhaust Radiation High High Instrumentation Not Performed;Work Order 00159564 Not Revised ML20059B9241993-12-15015 December 1993 Notice of Violation from Insp on 931122-23.Violation Noted:Licensee Shipped Container of Resins to Chem-Nuclear Waste Disposal Site Found,By Disposal Site Operator,To Contain 0.7% of Free Standing Liquid ML20059B4861993-12-10010 December 1993 Notice of Violation from Insp on 931024-1127.Violation Noted:On 931007,operators Hanging Clearances 933749 & 933750 Failed to Adequately Verify Inverter 1Y96 Was Being Supplied from Normal Power Supply ML20058J4991993-11-19019 November 1993 Notice of Violation from Insp on 930919-1023.Violation Noted:Undervessel Maint Personnel Disconnected 39 Addl LPRM Detectors Not Specified in Maint Work Order ML20059E6401993-10-26026 October 1993 Notice of Violation from Insp on 930927-1001.Violation Noted:On 930930,plant AO Entered Turbine Bldg Through Back Door of Control Room W/O Radiation Work Permit or self-reading Dosimeter ML20059G2631993-10-15015 October 1993 Notice of Violation from Insp on 920627-0731.Violation Noted:Licensee Determined That Records Required to Be Maintained by Commission Regulations or License Conditions Not Complete & Accruate in All Matl Respects ML20059A3871993-10-0808 October 1993 Notice of Violation from Insp on 930815-0918.Violation Noted:Instruction 07-S-13-60 Inadequate in That Instruction Did Not Adequately Address Setpoint of Slaved Trip Units Which Caused Unplanned RCIC Injection on 930914 ML20024H8631993-08-0606 August 1993 Notice of Violation from Insp on 930620-0717.Violation Noted:Ro Directed Scramming of Rod 28-53 from Original Position of Notch 08 Prior to Full Withdrawal ML20036B2241993-05-0707 May 1993 Notice of Violation from Insp on 930314-0417.Violation Noted:On 930402,reactor Operator Mistakenly Inserted Control Rod 56-45 Addl Notch During Operability Testing ML20125C6881992-11-24024 November 1992 Notice of Violation from Insp on 921001-1107.Violation Noted:Lubrication Requirements for Plant Equipment Determined by Use of Uncontrolled Document ML20059L4001990-09-0606 September 1990 Notice of Violation from Insp on 900721-0817.Violation Noted:Surveillance Procedure 06-IC-1C34-M-0001 Inadequate & Resulted in Feedwater Transient ML20043D8871990-05-0101 May 1990 Notice of Violation from Insp on 900414-0518.Violation Noted:Shift Superintendent Failed to Maintain Reactor Vessel Water Level 3 Trip Channel & /Or Trip Sys in Tripped Condition for Group 3 Channel B Isolation ML20042E1151990-04-0202 April 1990 Notice of Violation from Insp on 900217-0316.Violations Noted:Contamination of Makeup Water Sys & Unmonitored Release of Radioactive Effluent Resulted from Operator Actions on 900301 Due to Inadequate Sys Operating Procedure ML20006D5061990-01-31031 January 1990 Notice of Violation from Insp on 891216-900119.Violation Noted:On 891230,following Manual Reactor Scram,Unit Exceeded Max Reactor Cooldown Rate for Reactor Vessel Bottom Head Drain ML20005G1831990-01-0404 January 1990 Notice of Violation from Insp on 891118-1215.Violation Noted:Quality Deficiency Rept 237/89 Inadequately Reviewed ML20247G6791989-09-12012 September 1989 Notice of Violation from Insp on 890715-0825.Violation Noted:Filter Used for Determining Tech Spec Iodine Activity for Fuel Handling Area Vent Not Installed During 890719-26 & Semiannual Instrument Air Sample for 1989 Not Obtained ML20248C9561989-07-28028 July 1989 Notice of Violation from Insp on 890616-0714.Violations Noted: on 890620,operators Failed to Implement RCIC Sys Operating Instruction 04-1-01-E51-1 When Returning Sys to Standby Condition Following Maint ML20246B2671989-06-27027 June 1989 Notice of Violation from Insp on 890520-0616.Violations Noted:Licensee Failed to Procedurally Control Settings Which Resulted in Isolation When Damping Setting Not Made to New Circuit Boards Installed During Last Refueling Outage ML20245F5381989-06-13013 June 1989 Notice of Violation from Insp on 890415-0519.Violation Noted:Sys Operating Instruction 04-1-01-N21-1, Feedwater Sys Inadequate for Operation of Reactor Feedwater Pump Turbine Manual Speed Changer ML20244E0491989-05-31031 May 1989 Notice of Violation from Insp on 890329-31 & 0419-21. Violations Noted:On 890328,contract Worker Observed Entering Room in High Radiation Area W/O Being Provided W/Or Accompanied by One or More of Listed Requirements ML20247E7321989-03-16016 March 1989 Notice of Violation from Insp on 890114-0217.Violation Noted:Failure to Initially Perform Written Safety Evaluation Prior to Storage of Ecodex Resin in Containment ML20235K4581989-02-13013 February 1989 Notice of Violation from Insp on 890110-12.Violation Noted: Licensee Failed to Document All Emergency Preparedness Training Provided or Ensured to Offsite Support Agencies ML20204E9811988-10-0606 October 1988 Notice of Violation from Insp on 880820-0923.Violation Noted:Failure to Follow Administrative Procedure 01-5-06-1 to Evaluate Whether Opening Breaker Had Any Effect on Other Equipment & Plant Operation ML20153E6661988-05-0303 May 1988 Notice of Violation from Insp on 880319-0415.Violation Noted:Failure to Perform 10CFR50.59 Evaluation to Determine That Manual Operation of Pot Drain Valves on RCIC Supply Pipe Line Does Not Constitute Unreviewed Safety Question ML20151C1261988-04-0505 April 1988 Notice of Violation from Insp on 880220-0318.Violation Noted:Jumpered Terminals 9 to 10 on Ground Overcurrent Relay on Breaker 152-1609 Instead of 152-1606 & Failure to Document Installation of Equipment in Condenser Offgas Sys ML20150E5551988-03-25025 March 1988 Notice of Violation from Insp on 881214-18.Violation Noted: Licensee Installed Commercial Grade Parts on Equipment Requiring Environ Qualification W/O Adequate Evaluation of Suitability for Use in safety-related Applications ML20196K4411988-03-0303 March 1988 Notice of Violation from Insp on 880116-0219.Violation Noted:Licensee Failed to Follow Procedure 04-1-01-C11-1 to Properly Store Nitrogen Bottle Inside Containment ML20150C0691988-02-22022 February 1988 Notice of Violation from Insp on 871219-880115.Violation Noted:Dp for LPCS & LPCI Sys Not Determined & ECCS Header Delta Pressure Instrumentation Verified to Be 1.2 Plus/Minus 0.1 Psid from Calculated Dp IR 07100114/20120181988-01-20020 January 1988 Notice of Violation from Insp on 871114-1218.Violation Noted:Failure to Provide Necessary Controls to Ensure That Work & Testing Accomplished & Plant Conditions Maintained ML20195H7031988-01-0606 January 1988 Notice of Violation from Insp on 871214-17.Violation Noted: Dec 1987 Chemical Cleaning of Loops a & C of Standby Svc Water Sys Conducted W/O Adequate Safety Evaluation of Effect on Weld Matls & Crevice Regions in Piping IR 07100017/20110131987-11-25025 November 1987 Notice of Violation from Insp on 871017-1113.Violation Noted:Cold Weather Protection Procedure Had Been Signed Off as Completed & Portable Heaters or Grating Covers Not Installed ML20236M2741987-10-27027 October 1987 Notice of Violation from Insp on 870919-1016.Violation Noted:Failure to Document & Evaluate Test Discrepancies Noted on 870910 & 11 During Standby Liquid Control Sys Testing ML20237H1561987-08-28028 August 1987 Notice of Violation from Insp on 870718-0821.Violation Noted:Failure to Notify NRC within 1 H of Failure of Claiborne County Sirens & Tone Activated Receivers to Activate During Alert Notification Test ML20235H8701987-07-0808 July 1987 Notice of Violation from Insp on 870615-19.Violation Noted: Failure to Provide Required Training to Two Members of Emergency Organization ML20234E7731987-07-0101 July 1987 Notice of Violation from Insp on 870516-0619 ML20214A1181987-04-30030 April 1987 Notice of Violation from Insp on 870314-0417 ML20212R3471987-01-16016 January 1987 Notice of Violation from Insp on 870115-1219 1999-02-26 Category:TEXT-INSPECTION & AUDIT & I&E CIRCULARS MONTHYEARIR 05000416/19990121999-09-29029 September 1999
[Table view]Insp Rept 50-416/99-12 on 990725-0904.Violations Noted.Major Areas Inspected:Licensee Operations,Maint,Engineering & Plant Support IR 05000416/19990111999-09-28028 September 1999 Insp Rept 50-416/99-11 on 990830-0903.No Violations Noted. Major Areas Inspected:Solid Radioactive Waste Management Program,Radioactive Matl Transportation Program,Facilities & Equipment,Staff Knowledge & Performance & Staff Training IR 05000416/19990141999-09-27027 September 1999 Insp Rept 50-416/99-14 on 990830-0903.No Violations Noted. Major Areas Inspected:Implementation of Liquid & Gaseous Radioactive Waste Effluent Mgt Program & Status of Effluent Radiation Monitors & Counting Room Instruments IR 05000416/19990151999-09-13013 September 1999 Partially Withheld Insp Rept 50-416/99-15 on 990816-20. Noncited Violation Noted.Major Areas Inspected:Licensee Physical Security Program,Personnel Access Control,Access Authorization & Protected Area Detection Aids IR 05000416/19990101999-08-24024 August 1999 Insp Rept 50-416/99-10 on 990809-13.No Violations Noted. Major Areas Inspected:Licensed Operator Requalification Program IR 05000416/19990091999-08-0909 August 1999 Insp Rept 50-416/99-09 on 990613-0724.No Violations Noted. Major Areas Inspected:Licensee Operations,Maint,Engineering & Plant Support IR 05000416/19990031999-07-30030 July 1999 Insp Rept 50-416/99-03 on 990405-08 & 0510-11.No Violations Identified.Major Areas Inspected:Corrective Action Program Implementation IR 05000416/19990071999-07-23023 July 1999 Insp Rept 50-416/99-07 on 990622-25.Violations Noted.Major Areas Inspected:Announced Insp of Licensee Performance & Capabilities During full-scale,biennial Exercise of Emergency Plan & Implementing Procedures Performed IR 05000416/19990081999-07-15015 July 1999 Insp Rept 50-416/99-08 on 990502-0612.Violations Noted.Major Areas Inspected:Licensee Operations,Maint,Engineering & Plant Support IR 05000416/19990051999-06-27027 June 1999 Insp Rept 50-416/99-05 on 990321-0501.Violations Identified, Being Treated as non-cited Violations.Major Areas Inspected: Aspects of Licensee Operations,Maint,Engineering & Plant Support IR 05000416/19990061999-05-21021 May 1999 Insp Rept 50-416/99-06 on 990419-23.No Violations Noted. Major Areas Inspected:Licensee Implementation of NRC Approved Fire Protection Program IR 05000416/19990021999-05-18018 May 1999 Insp Rept 50-416/99-02 on 990222-26 & 0308-12.Non-cited Violations Noted.Major Areas Inspected:Engineering IR 05000416/19990041999-04-23023 April 1999 Insp Rept 50-416/99-04 on 990131-0320.Violations Noted. Major Areas Inspected:Operation,Maintenance,Engineering & Plant Support IR 05000416/19990011999-02-26026 February 1999 Insp Rept 50-416/99-01 on 990201-05.Violations Noted. Major Areas Inspected:Plant Support.Violation of TS 5.7.2 Identified for Failure to Control Locked High Radiation Area Around Spent Fuel Pool Cooling & Cleanup HX ML20207E0881999-02-26026 February 1999 Notice of Violation from Insp on 990201-05.Violation Noted: on 990201,NRC Inspectors Identified That Area with Dose Rates Greater than 1000 M/H Not Provided with Locked or Continously Guarded Doors to Prevent Unauthorized Entry IR 05000416/19980151999-01-20020 January 1999 Insp Rept 50-416/98-15 on 981101-1212.No Violations Noted. Major Areas Inspected:Licensee Operations,Maint,Engineering & Plant Suuport PNO-IV-99-005, on 990113,Grand Gulf Operators Commenced Unit Shutdown,From 100 Percent Power,Due to One or More Apparently Degraded Current Transformers Located in Safety Related Div I,4.16 Kv Switchgear.State of Ms Informed1999-01-13013 January 1999 PNO-IV-99-005:on 990113,Grand Gulf Operators Commenced Unit Shutdown,From 100 Percent Power,Due to One or More Apparently Degraded Current Transformers Located in Safety Related Div I,4.16 Kv Switchgear.State of Ms Informed IR 05000416/19980161998-12-24024 December 1998 Insp Rept 50-416/98-16 on 981207-11.Violations Noted.Major Areas Inspected:Operational Status of Licensee Emergency Preparedness Program Was Conducted ML20198L7711998-12-24024 December 1998 Notice of Violation from Insp on 981207-11.Violation Noted: on 950630,licensee Made Change to Emergency Plan Without Commission Approval ML20196F1141998-12-0101 December 1998 Notice of Violation from Insp on 980920-1031.Violation Noted:From 980521 Through 981015,conditions Adverse to Quality Identified in Condition Rept 1998-0014 Not Promptly Corrected ML20196F1271998-12-0101 December 1998 Insp Rept 50-416/98-13 on 980920-1031.Violations Noted.Major Areas Inspected:Operations,Maint,Engineering & Plant Support IR 05000416/19980141998-11-27027 November 1998 Insp Rept 50-416/98-14 on 981026-30.No Violations Noted. Major Areas Inspected:Exposure Controls,Controls of Radioactive Matls & Contamination,Surveying & Monitoring & Quality Assurance Oversight of Radiation Protection Program IR 05000416/19980111998-10-14014 October 1998 Insp Rept 50-416/98-11 on 980809-0919.No Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support IR 05000416/19980121998-09-15015 September 1998 Insp Rept 50-416/98-12 on 980817-20.No Violations Noted. Major Areas Inspected:Training,Qualifications,Quality Assurance Oversight,Facilities & Equipment & Annual Reports IR 05000416/19980031998-09-0909 September 1998 Insp Rept 50-416/98-03 Cancelled IR 05000416/19980091998-08-31031 August 1998 Insp Rept 50-416/98-09 on 980628-0808.No Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support IR 05000416/19980101998-08-26026 August 1998 Insp Rept 50-416/98-10 on 980803-07.No Violations Noted. Major Areas Inspected:Licensee Physical Security Program IR 05000416/19980081998-07-14014 July 1998 Insp Rept 50-416/98-08 on 980517-0627.No Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support IR 05000416/19980071998-06-0202 June 1998 Insp Rept 50-416/98-07 on 980518-21.No Violations Noted. Major Areas Inspected:Access Authorization,Alarm Stations, Communications,Access Control of Packages & Vehicles, Assessment Aids & Mgt Support IR 05000416/19980051998-05-28028 May 1998 Insp Rept 50-416/98-05 on 980405-0516.Violations Noted.Major Areas Inspected:Licensee Operations,Maint,Engineering & Plant Support ML20248E7501998-05-28028 May 1998 Notice of Violation from Insp on 980405-0516.Violation Noted:On 980421,inspectors Found Back Doors on Diesel Generator Control Cabinet 1H22-p400 in Div 1 Standby Diesel Generator Room Standing Wide Open & Unattended IR 05000416/19980061998-05-19019 May 1998 Insp Rept 50-416/98-06 on 980427-0501.No Violations Noted. Major Areas Inspected:Radiation Protection Activities in Support of 1998 Refueling Outage IR 05000416/19980041998-05-0505 May 1998 Insp Rept 50-416/98-04 on 980414-16.No Violations Noted. Major Areas Inspected:Maint & Plant Support IR 05000416/19983011998-04-16016 April 1998 Insp Rept 50-416/98-301 on 980330-0403.No Violations Noted. Major Areas Inspected:Competency of Reactor Operator & Eight Senior Applicants for Issuance of OLs at Grand Gulf Nuclear Station IR 05000416/19980021998-04-15015 April 1998 Insp Rept 50-416/98-02 on 980222-0404.No Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support IR 05000416/19980011998-03-0404 March 1998 Insp Rept 50-416/98-01 on 980111-0221.No Violations Noted. Major Areas Inspected:Operations,Maintenance,Engineering & Plant Support IR 05000416/19970221997-12-15015 December 1997 Insp Rept 50-416/97-22 on 971130-980110.No Violations Noted. Major Areas Inspected:Operations,Maint,Engineering IR 05000416/19970211997-12-0505 December 1997 Insp Rept 50-416/97-21 on 971019-1129.Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant Support ML20199L9411997-11-25025 November 1997 Notice of Violation from Insp on 970804-22.Violation Noted: on or About Period of 970117-29,approved FP Program as Described in UFSAR Was Not Fully Implemented.Emergency Light 1T92S222A Was Not Capable of Performing Function IR 05000416/19970181997-11-25025 November 1997 Insp Rept 50-416/97-18 on 970804-22.Violations Noted.Major Areas Inspected:Operations & Maint.Nrc IP 40500 Used to Evaluate Licensee Effectiveness in Identifying,Resolving & Preventing Issues That Degrade Quality of Plant Operations IR 05000416/19970201997-10-31031 October 1997 Insp Rept 50-416/97-20 on 970907-1018.Violations Noted.Major Areas Inspected:Operations,Maint & Plant Support Re Emergency Post Accident Sampling Sys Drill ML20198Q0291997-10-31031 October 1997 Notice of Violation from Insp on 970907-1018.Violation Noted:As of 971011,security Patrols Had Not Reported Dark Areas in Temporary Covered Maint Work Area in Protected Area IR 05000416/19970161997-10-23023 October 1997 Insp Rept 50-416/97-16 on 970929-1003.No Violations Noted. Major Areas Inspected:Review of Licensed Operator Requalification Program Following Guidelines in IP 71001 IR 05000416/19970151997-10-0909 October 1997 Insp Rept 50-416/97-15 on 970916-19.Three Weaknesses Noted During Exercise.Major Areas Inspected:Licensee Performance & Capabilities During full-scale,biennial Exercise of Emergency Plan & Implementing Procedures IR 05000416/19970071997-10-0101 October 1997 Informs That Insp Rept 50-416/97-07 Has Been Cancelled & There Will Be No Insp Issued for This Rept Number ML20216J2081997-09-12012 September 1997 Notice of Violation from Insp on 970803-0906.Violation Noted:As of 970811,duplex Filter Selection Levers for HPCS & Div 1 Standby DGs Were in Both Position Such That Two Strainers/Filters Were Selected IR 05000416/19970171997-09-0505 September 1997 Insp Rept 50-416/97-17 on 970804-08.No Violation Noted.Major Areas Inspected:Implementation of Solid Radwaste Mgt & Radioactive Matls Transportation Programs ML20210N0761997-08-19019 August 1997 Notice of Violation from Insp on 970622-0802.Violation Noted:On 970630,inspectors Identified Extension Ladder Supported on safety-related Cable Tray & No Engineering Evaluation Had Been Completed IR 05000416/19970131997-08-0606 August 1997 Partially Withheld Insp Rept 50-416/97-13 on 970714-18 (Ref 10CFR73.21).Violations Noted.Major Areas Inspected: Licensee Physical Security Program,Including Review of Records,Repts,Testing,Maint & Assessment Aids ML20216A8411997-08-0606 August 1997 Notice of Violation from Insp on 970714-18.Violation Noted: on 970717,compensatory Measures Not Implemented at Two Trailers within Protected Area Where Lighting Did Not Meet Required 0.2 Footcandles 1999-09-29 |
Text
'(
.n.-
..w.., +q..
.--c
../
'p APPENDIX'A-NOTICE OF VIOLATION Mississippi Power-and Light Company License No. DPPR-118 Grand-Gulf.
-Based on the NRC inspection August 4-29, 1980, certain of your activities were apparently not: conducted in full-compliance with NRC requirements as ' indicated below. These items have been categorized as described in currespondence to.you dated December 31, 1974.
-As required by Criterion V ofl Appendix B to 10 CFR 50, implemented by Mississippi Power anrE Light Company's PSAR, Section 17.1.5.2 Bechtel's activities : affecting quality shall be accomplished in accordanceL.with instructions,. procedures and drawings.
Bechtel-Nuclear Components Division I, Part III' Procedures Paragraph ~ 6.4 states that electrodes shall be issued in portable rod warmers. Return unused portions at.the end of the shift.
Contrary to the above, on August '14, '1980, the inspector found approximat'ely 25 unused electrodes -lying loose in the containment building.
This is a deficiency.