05000338/LER-1980-098-03, /03L-0:on 801123,while Operating in Mode 1,neutron Flux Distribution Exceeded Axial Flux Difference Target Band.Caused by Xenon Transient.Control Rods Inserted,Causing Flux Distribution to Shift Downward

From kanterella
(Redirected from ML20002B015)
Jump to navigation Jump to search
/03L-0:on 801123,while Operating in Mode 1,neutron Flux Distribution Exceeded Axial Flux Difference Target Band.Caused by Xenon Transient.Control Rods Inserted,Causing Flux Distribution to Shift Downward
ML20002B015
Person / Time
Site: North Anna 
Issue date: 12/04/1980
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20002B014 List:
References
LER-80-098-03L, LER-80-98-3L, NUDOCS 8012090319
Download: ML20002B015 (2)


LER-1980-098, /03L-0:on 801123,while Operating in Mode 1,neutron Flux Distribution Exceeded Axial Flux Difference Target Band.Caused by Xenon Transient.Control Rods Inserted,Causing Flux Distribution to Shift Downward
Event date:
Report date:
3381980098R03 - NRC Website

text

o

?.

J k

D U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BLOCK-/ /'/ / / / / (1)

(PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)

/0/1/

_/V/A/N/A/S/1/ (2)

/0/0/-/0/0/0/0/0/-/0/0/ (3)

/4/1/1/1/1 (4)

/ / / (5)

LICENSEE CODE LICENSE NUMBER LICENSE TYPE CAT LL/-(6)

,/0/5/0/0/0/3/3/8/ (7)

/1/1/2/3/8/0/

(8) /1/2/o/4/8/o/ (9)

' DOCKET NUMBER EVENT DATE REPORT DATE EVENT' DESCRIPTION AND PROBABLE CONSEQUENCES (10)

~/0/2/

/

On November 23, 1980 while operating in Mode 1 at 83% power, the neutron flux /

/0/3/

/

distribution exceeded the 15% axial' flux difference target band. Since the

/

7 I

/0/4/

/

power distribution was brought back inside the target band in 2 minutes, the

/

{

/0/5/

/

health and safety of publir were not affected. The applicable T.S. is 3.2.1,

/

/0/6/

/

and the event is reportable pursuant to T.S. 6.9.1.9.b.

/

/0/7/

/

/

i

/0/8/

/

/

L SYSTEM

CAUSE

CAUSE COMP.

VALVE j

CODE CODE SUBCCDE COMPONENT CODE SUBCODE SUBCODE

/0/9/

/R/C/ (11) /X/ (12). /X/ (13) /Z/Z/Z/Z/Z/Z/-(14) g/ (15)

LZ/ (16)

SEQUENTIAL OCCURRENCE REPORT REVISION i

LER/R0 EVENT YEAR REPORT NO.

CODE TYPE NO,

{

-(17) REPORT NUMBER

/8/0/

/-/ /0/9/8/

/\\/

/0/3/

/L/

/-/

/0/

1 ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP. COMPONENT TAKEN ACTION ON PLANT METHOD HOURS SUBMITTED FORM SUB. SUPPLIER MANUFACTURER

]

[X/ (18) LZ/ (19) /Z/ (20) /Z/ (21) /0/0/0/0/ (22) /Y/ (23) /N/ (24) /N/ (25) /W/1/2/0/ (26) :

CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)

/1/0/

/

The transgression of the axial flux difference target band is attributed to a /

[l/,

/

xenon transient. The corrective action was to insert control rods thereby

/

i/2/

/

causing the flux distribution to shift cownward.

/

/1/3/

/

/

}

/1/4/

/

/

FACILITY METHOD OF STATUS

% POWER OTHER STATUS

/ (30) DISCOVERY DISCOVERY DESCRIPTION (32)

/1/5/

LE/ (28)

/0/8/3/ (29) /

NA LA/ (31)

/ OPERATOR OBSERVATION /

ACTIVITY CONTENT RELEASED OF RELEASE. AMOUNT OF ACTIVITY (35)

LOCATION OF RELEASE (36) l

/1/6/

LZ/ (33)

- LZ/ (34) /

NA

/

/

NA

/

3 PERSONNEL EXPOSURES NLdBE - -

TYPE DESCRIPTION (39)

/1/7/ /0/0/J/ (37) /Z/ (38) /

NA-

/

i

?

PERSONNEL INJURIES NUMBER DESCRIPTION (41) t

/1/8/ /0/0/0/ (40) /

NA

/

LOSS OF OR DA11 ACE TO FACILITY G3)

TYPE

DESCRIPTION

}{

./1/9/

/Z/ (42) /

NA

/

PUBLICITY ISSUED DESCRIPTION (45)

NRC USE ONLY

/2/0/

/N/.(44) /

NA

/////////////

NAME OF IREPARER W. R. CARTWRIGHT PHONE

('03) 894-5151

'80120903/7,

.l

I W

A Virginia Electric and Power Company.

North Anna Power Station, Unit #1 Attachment: Page 1 of 1 Docket No. 50-338 Report No. LER 80-098/03L-0

Description of Event

7 On November 23, 1980 while operating in Mode 1 at 83% power, the neutron flux distribution exceeded the 15% axial flux difference target band.

{-

Probable Consequences of Oct.urrence Since the power distrtbution was brought back inside the target band in 2 minutes, the her.lth and safety of the public were not affected.

Cause of Event

The transgression of the axial flux difference target is attributed to a xenon transient.

Immediate Corrective Action

The immediate corrective action was to insert control rods and cause flux distribution to shift downward.

Scheduled Corrective Action

]

There are no scheduled corrective actions.

Actions Taken to Prevent Recurrence 4

No further actions are required.

Generic Implications There are no generic implications.

i 1

9 i

I i

i

--w-w

,-e

,e, no e

,-ne

-,,nr.-

--,nn.-