M

[

%o, UNITED STATES j

~* 7, NUCLEAR REGULATORY COMMISSION 2

E REGION lli 799 ROOSEVELT ROAD o,

GLEN ELLYN,lLLINOIS 60137

'j g

j#

}{,'j g \\

MAR 20.looi

~ '2p x

?? l5

-\\

~.

y z:-

Illinois Department of

.~_.'" 85

~

l

~

- Y.

G, 'Q(' S 2 *df 837,D Nuclear Safety f6 ATTN:

Mr. Gary N. Wright 1035 Outer Park Drive

'" j

' ',, )

'+

Deputy Director h(,N Springfield, IL 62704 8ts Gentlemen:

The enclosed IE Information Notice No. 81-08 titled " Repetitive Failures of Limitorque Operator SMB-4 Motor-To-Shaft Key" was sent to the licensees listed below on March 20, 1981:

American Electric Power Service Corporation Indiana and Michigan Power Company D. C. Cook 1, 2 (50-315, 50-316)

Cincinnati Gas & Electric Company Zimmer (50-358)

Cleveland Electric Illuminating Company Perry 1, 2 (50-440, 50-441)

Commonwealth Edison Company Braidwood 1, 2 (50-456, 50-457)

Byron 1, 2 (50-454, 50-455)

Dresden 1, 2, 3 (50-10, 50-237, 50-249)

LaSalle 1, 2 (50-373, 50-374)

Quad-Cities 1, 2 (50-254, 50-265)

Zion 1, 2 (50-295, 50-304)

Consumers Power Company Big Rock Point (50-155)

Midland 1, 2 (50-329, 50-330)

Palisades (50-255)

Dairyland Power Cooperative LACBWR (50-409)

Detroit Edison Company Fermi 2 (50-341)

Illinois Power Company Clinton 1, 2 (50-461, 50-462)

Iowa Electric Light & Power Company Duane Arnold (50-331) 810 6 2 :10Ils/

Oc,

lp i

' Illinois Department'of-

.2-Nuclear Safety b

7, Northern Indiana Public Service Company Bailly (50-367)

L Northern States Power Company Monticello (50-263)

' Prairie-Island 1,'2 (50-282, 50-306)

Public Service of Indiana Marble Hill 1,'2 (50-546, 50-547)

Toledo Edison Company Davis-Besse 1 (50-346) 2 Union Electric Company Callaway.1, 2-(50-483, 50-486)

~ Wisconsin Electric Power Company Point Beach 1, 2 (50-266, 50-301)

Wisconsin Public Service Corporation Kewaunee (50-305)

Sincerely,

\\

idyY'dr er"#b J

1, t

Uord Processing and Document Control Section

Enclosure:

IE Information Notice No. 81-08 cc w/ encl:

Mr. D. W. Kane,.

Sargent & Lundy Central Files Reproduction Unit NRC 20b AEOD.

Resident Inspectors, RIII J. G. Keppler,- RIII C. E. Norelius,-RIII R. F.-Heishman, RIII J. A.(Hind, RIII-P. R. Wohld, RIII-PDR Local PDR NSIC LTIC t

---e v-

t, SSINS No.: 6835 Accession No.:

i 8011040272 IN 81-08 UNITED STATES NUCLEAR REGULATORY COMMISSION 0FFICE OF-INSPECTION AND ENFORCEMENT l-March 20, 1981 IE INFORMATION NOTICE NO 81-08:

REPETITIVE FAILURES OF LIMITORQUE OPERATOR SMB-4 MOTOR-T0-SHAFT KEY

-Description of Circumstances:

l During normal surveillance testing of motor-operated valves at the Cooper

~

l Nuclear Station, it was discovered that the RHR "B" loop suppression pool i

cooling inboard. throttle valve would not'. operate.

The valve did not operate

-because the key between the motor pinion gear and the motor shaft had failed.

.The operator for the valve has been identified as being Limitorque model SMB-4.

Analysis of the failed key revealed that a standard type 1010 steel key had been_ installed instead of the required special. type 4140 cteel key.

I'

'Further review of the problem established that similar failures with motor-to-shaf t keys.had also taken place at the Pilgrim, Hatch, and Fitzpatrick-nuclear power facilities.

Limitorque Company has performed an evaluation of the problem, and they have concluded that the problem is confined to operators having a torque rating in excess of 100 ft/lb.

The standard-type 1010 steel possesses adequate strength to accommodate motor operators having a torque rating that is less than 100 ft/lb.

Recommended Action for Holders of Operating Licenses and Construct b n Permits:

(

It is recommended that licensees having Limitorque Operator SMB-4 installed in their facilities verify that the special type 4140 steel keys have been used.

This can be easily accomplished by performing a hardness check of the motor-to-shaft keys during-the next scheduled surveillance testing.

[

No written rbsponse to this information notice is required.

If you need additional information with regard to this subject, please contact the Director of the i

appropriate NRC Regional Office.

Attachment:

Recently issued IE Information Notices

4:

-Attachment IN 81-08 March 20, 1981 RECENTLY ISSUED IE'INFORMATION NOTICES

'Information-Date of

' Notice No.

Subject

-Issue Issued to-81-07J Pot'ential Problem with 3/16/81

'All power reactor Water-Soluble Purge Dam facilities with an_

Materials Used During OL or CP

' Inert Gas Welding 81-06 Failurelof ITE Model 3/11/81 11' power reactor K-600 Circuit Breaker facilities with an OL or CP-81-05 Degraded DC~ System at 3/13/81 All power reactor Palisades facilities with an.

' OL cr CP 81 Cracking in Main Steam 2/27/81 All power. reactor Lines' facilities with an OL

'81-03

. Checklist for Licensees 2/12/81 All power reactor Making Notifications of facilities with an Significant Events in OL Accordance with 10 CFR 50.72 81-02 Transportation of 1/23/81 All Radiography Radiography Devices licensees 81-01 Possible Failures of 1/16/81 All power reactor General Electric Type facilities with an HFA Relays OL or CP.

80-45 Potential Failure of 12/17/80 All PWR facilities BWR Backup ~ Manual Scram with an OL-or CP Capability 80-44 Actuation of ECCS in the 12/16/80 All PWR facilities Recirculation Mode While' with an OL or CP in Hot Shutdown

'OL = Operating Licenses.

CP = Construction Permi.s r