ML19350D915

From kanterella
Jump to navigation Jump to search
Notifies That 801029 Potential Deficiency Re Industrial Mechanics,Inc Anchor Nuts & Bolts Is Not Reportable Per 10CFR50.55e.No Defective Anchor Nuts & Bolts Were Found.No Significant Reduction in Safety Exists
ML19350D915
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 12/18/1980
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Siedle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, KMLNRC-049, KMLNRC-49, NUDOCS 8105260425
Download: ML19350D915 (1)


Text

l t

.o,

/

/

t KANSAS GAS AND ELECTRIC COMPANY

% etac-=.c c::u.eu ace== cwossta=

g o

e af.y LD

-y 2

MAY 2 21981

  • s--

D*cember 18, 1980 h_4 4s assa^ross p?

u.a. Hua sca*iss a

(

Mr. W.C. Seidle, Chief Reactor Construction and

'4

'5' Engineering Support Branch

  1. w i

U.S. Nuclear Regulatory Cczunission C.

Region IV

' ' ~ ~ ~

611 Ryan Plaza Drive - Suite 1000 Arlington, Texas 76012 KMLNRC-049 Re:

a) NRC Docket No. 50-482 b) GKoester letter to WSeidle,KMLNRC-011 c) GKoester letter to WSeidle,K'tRIRC-033 Subj: Potential 50.55(e) Report Industrial Mechanics, Inc. - Nuts and Bolts

Dear Mr. Seidle:

As indicated in my letter of October 29,1980 (Reference c), analysis of data derived from anchor bolts and nuts, with out-of-tolerance thread sizes, has been completed by our A/E, Bechtel. The nonconforming nuts and bolts were furnished by Industrial Mechanics, Inc. under Specification 10466-C-134.

The report indicates that of the nuts and bolts checked, not a single anc.'ior (nut-bolt combination) was found for which the predicted failure mode is in the threads. This results in no predicted reduction in design capacity.

We have concluded that had the out-of-tolerance nuts and bolts ramMned undetected there would not have been a significant reduction in safety.

We, therefore, no longer consider this matter to be a potential 10CFR50.55(e) item.

The final Bechtel report is in our possession and may be reviewed by NRC inspectors during any future inspection.

Yours very truly, 8103260 M bhat K A 3

GI.K:bb g6Ii cc: TVandel (NRC Site Inspector)

,g 201 N. Market - Wictura Kansas - Mad Address: RO. Box 208 i Mctuta. Kansas 67201 - Teleonone: Area Coce (316) 2616451