1 south CARouwA ELECTRIC a GAS COMPANY SOST OFFICE Son fee Cotum si A, south CAnouM A 29218 T. C. N a c Mc Ls. J n.

v.ci e.u........ o.

c.acue,.i March 10, 1981 i'#'

on o. c..,...

e \\/

pFH,s'j@.

k 1

b81 h 1 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission M g g ress Region II, Suite 3100 101 Marietta Street, N. W.

9 y'l Atlanta, Georgia 30303 y

"sy -

Subject:

Virgil C. Summer Nuclear Station Docket No. 50/395 Potential Substantial Safety Hazard Interim Report Nuclear Eng. File 3.1051

Dear Mr. O'Reilly:

On February 4, 1981, Mr. John Rausch of NRC Region II was notified of a potential significant deficiency under 10CFR50.55(e) concerning mcfsture in component cooling pump motor lA.

This letter provides an inte. rim report on this item.

Electrical maintcaance found the component cooling pump motor lA to be wet and upon meggering the stator coils, it was found to be grounded.

The motor was wiped dry and external heat was applied per Westinghouse instructions. After drying the motor, the megger readings on the motor were good. However, earlier history on the motor showed that the motor was inad-vertently run without cooling water. The motor was manufactured by Westinghouse.

A decision has been made to reinsulate the stator windings to insure the integrity of the motor. Specific details required by 10CFR50.55(e) will be given in a final report.

r tuly yours, ichols, Jr./W TB:TCN:glb cc: Page Two

\\kWo 8103170g{

i

4 Mr. Jcmes P. O'Reilly March 6, 1981 Page Two cc:

V. C. Su=:ner G. H. Fischer T. C, Nichols, Jr.

O. W. Dixon, Jr.

C. A. Price D. A. Nauman W. A. Williams, Jr.

R. B. Clary A. R. Koon A. A. Smith H. N. Cyrus J. B. Fnotts, Jr.

J. L. Skolds B. A. Bursey O. S. Bradham Document Management Branch (55e/21/LER Only)

I&E (Washington)

ISEG PRS NPCF File e

d e

ut