ut r)
\\ ipi 9 -)
C
,3 mq mmw;l 7:.y;.;537t537gyg" 2,7;;;X x,;.M r ' "'
d f
[f hk.)
s
.i I'
N' fdb?Nash.cM81-/,,
MN h---
c.
i e
R20Pnipijj;.o VEC114(1222)(1-016616C079)PD 03/20/75 1
TLX CONSPOWER JKN ZCZC 004 DLY J ACKSON MICHIG AN 3-20-75 Mp m..m.../-dMA,ig, PMS J G KEPPLER, USNRC - I&E
[........
799 ROOSEVELT RD
-.n-~"
-GLENELLYN,ILd8/89 hh o-* '
Yi-
-/
r-Oni tir...hO M'S N-h NEEND
..(fT&f' r~
RE:
DOCKET 50-155 THIS ABNORMAL OCCURRENCE REPORT A0-08-75 IS BEIhG SENT TO YOU TO
[j p CONFIRM THE TELEPHONE CALL TO' D. KILEY AT 1500 ON MARCH '19,' 1975 BY D. E. DE MOOR.
- 6. n l!
I l' O
- 1. REPORT NO A0-08-75 DOCKET 50-155 l 1 l
O u.,=, our REPORT DATE - MARCH 20, 1975 i,
2B.
OCCURRENCE DATE - MARCH 18, 1975 - CLASSIFIED AS ABNORMAL OC-CURRENCE ON MARCH 19, 1975.
i l
3.
FACILITY - BIG ROCK P0' INT PLANT, CHARLEVOIX, MICHIGAN l :
4.
IDENTIFICATION OF OCCURRENCE - CONTAINMENT VENTILATION SUPPLY
ALVE LEAK TEST FAILURE.
5.
CONDITION PRIOR TO OCCURRENCE - PLAhT IN COLD SHUTDOWN FOR MAINTENANCE AND TESTING.
l 6.
DESCRIPTION OF OCCURRENCE - DURING THE SEMIANNUAL COMPONENT 1
l
,,,,, Q K RATE TESTING OF THE SPHERE VENTILATION SUPPLY VALVES, EXCES-l Plo300 %
. v.w 3;m....,... m s.w:gmmgggy;y y y.-
.n.=
,p
. h?
hlb e
P s y; m ->u:u J h w w w w w = 4 & 2 n u..W c
- m. s=n. __,
y w
ff.\\70 3,70 e
~
SIVE LEAKAGE WAS NOTED.
PACKING LEAKS WERE SUSPECTED ON THE OUTER SUPPLY VALVE CV-4096.
HOWEVER, PACKING ADJUSTMENT OF CV-4096 AND
^
RETESTING INDICATES THAT THE PROBABLE SOURCE OF LEAKAGE IS ASSOCI-ATED WITH THE INNER SUPPLY VALVE CV-4097 SEAT.
INVESTIGATION IS CONTINUING THIS DATE.
7, 7.
DESIGNATION OF APPARENT CAUSE OF OCCURRENJF, - EXACT CAUSE UN-O KNOWN AT THIS TIME.
O 8.
ANALYSIS OF' OCCURRENCE - TESTING TO DATE INDICATES THAT ONLY' ONE OF THE TWO VALVES IN SERIES HAS EXCESSIVE LEAKAGE AT THE VALVE. SEAT UNDER SUCH CONDITIONS," THE CONTAINMENT INTEGRITY WOULD REMAIN INTACT
.O
~
AND NO UNDUE HAZARDS EXIST.,
O u.,=, -
9.
CORRECTIVE ACTION - INVESTIGATION CONTINUING.
CC:
DIV 0F REACTOR LICENSING, USNRC, WASH i
C J HARTMAN, BIG ROCK POINT I
R B SEWELL NUCLEAR LICENSING ADM CONSUMERS POWER CO ALL H0 i
NNNN MAR 2 4 1975 sF tact (R549)