YAlll[EE ATOUIC ELECil?IC COUPAllY iOM&+
k Rowe, Massachusetts 01367 Q?'
f
,Ya"[ massy tz g vp ;-:'
September 8, 1975 iQ s V
\\, =\\ '
b,>lp
~
e i 4 *, ~,. v 4
O United States Nuclear Regulatory Commission Office of Inspection & Enforcement Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 Attention: Mr. James P. O'Reilly, Director
Dear Mr. O'Reilly:
Pursuant to the requirements of the Technical Specifications Section E.4.d, a failure of an engineered safety feature that causes or threatens to ceuse the feature or system to be incapable of performing its intended function is reported as Abnormal Occurrence 50-29/75-09.
At 0720 on 9/6/75, with the plant ooerating at normal steady state power, a blown fuse in the'No.1 Emergency Diesel Generator DC starting circuit resulted from the overheating and subsequent fusing of a starting circuit supervisory lamp.
Immediately after the incident the No. 2 and Mc. 3 Emergency Diesel Generators were started and test run for five minutes thus veri-fying their operability.
At 1006 the same day a repair was completed and the No.1 Emergency Diesel Generator was test run and declared fully operational.
l A formal 10 day report will follow.
Very truly yours,
l
.Ydf hs 0v6 l
Herbert A. Autio Plant Superintendent NNS/jb cc: (2) Director, Office of MIPC U.S. Nuclear Regulatory Commission Washington, D. C. 20545 l
9/09/90 D9/
~
Ii a
YACHEE ATCDia ELECTDES CCDPAUV WlUk Rowe,Mmm-husetts 0139 Y/N'eKiSE
~
September 8.1975 United States-Nuclear Regulatory Cocs:rission Office of Inspection a Enforcement Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 Attention:
Mr. Jaces P. O'Reilly. Director
Dear Mr. O'Reilly:
. Pursuant to the requirecents of the Technical Specifications Section E.4.d, a failuru of an engineered safety feature that causes or threatens to cause the feature or system to be incapable of perforcing its intended functiorr is reported as Abnorte,a1 Occurrence 53-29/75-09.
At 0720 on 9/S/75, with the plant operating at norr.31 steady state. power, a blorn fuse in the No.1 Erercency Diesel Generator DC starting circuit resulted from the overheating and subsequent fring of a starting circuit supervisory lanp.
Icrediately after the incident the No. 2 and No. 3 Er.nrgency Diesel Generatcis ware started and test run for five minutes thus veri-fying their operability.
At 1005 the same day a repair was co~pleted and the No.1 Emergency Diesel Generator was test run and. declared fully cperational.
i A formal 10 day report wi1T fo1 Tow.
Very truly yours, I