Date released: 12/27/2019 Download: ML19347F838


Updated LER 81-021/03X-1:on 810217,boron Injection Tank Was Found to Contain Boron Concentration Below Tech Spec Limit. Caused by Leak Past Check Valve 2-CH-155,located in Boric Acid Supply Line.Check Valve Will Be Replaced
ML19347F840
Person / Time
Site: North Anna 
Issue date: 05/20/1981
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19347F840 (2)
Forwards Updated LER 81-021/03X-1
ML19347F837
Person / Time
Site: North Anna 
Issue date: 05/20/1981
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: OREILLY J D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19347F837 (1)