Forwards Info Re Line Routings & Calculations,In Response to Informal NRC Question Re Flashing in ECCS Suction Lines. Sargent & Lundy Re Calculation Assumptions Encl
ML19347F581
Person / Time
Site: LaSalle  
Issue date: 05/18/1981
From: Delgeorge L
COMMONWEALTH EDISON CO.
To: Schwencer A
Office of Nuclear Reactor Regulation
References
NUDOCS 8105200203
Download: ML19347F581 (6)


Text

{{#Wiki_filter:> -.. O Ona First h!ational Ptua. Chicigo. Ilknois x Commonwealth Edison N Address Reply to: Post Office Box 767 Chicago. Illinois 60690 r q% 1gep* 4,';;{..S.p, " Q May 18, 1981 e /y g

  1. g1 ( n (J Mr. A. Schwencer, Chief Licensing Branch 2 Division of Licensing U.S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

LaSalle County Station Units 1 and 2 Response to Informal NRC Question Regicaing Flasning In ECCS Suction Lines NRC Docket Nes. 50-373/374

Dear Mr. Schwencer:

In oraer to resolve a question raiscj by Mr. W. Hodges of the Reactor Systems Branch regarding the potential for flashing i n the LaSalle County ECCS suction lines, the enclosea information is submittea. This transmittal accuments information provicea in a conference call with Messrs. A. Bournia and W. Hodges, and discusses

  • line routings ano calculations performed incluaing all assumotions and cata requireo.

In aadition, sheet 6 of ar.islyt ic al; RH-9 7 and sheet 1 of analytical RH-37 are enclosed to iaentify tne routing of the point chosen for this discussion. That point was chosen to be the highest elbow locatea the greatest distance from the suppression pool in the ECCS line with the longest equivalent length (LPCI suction line B). A minimum margin of 12.1 feet of heaa exists for this limiting elbow. If there are any further questions in this regara, please airect them to this office. In as much as there is no formal question in this subject, FSAR documentation will not be made. Forty copies of this letter and the ariclosure are proviced for your use. Very truly yours, ..-/ s v., .u.7 L. O. DelGeorge Nuclear Licensing Aaministrator cc: NRC Resident Inspector - LSCS QooI s 2023N I( ll 810Q00$()J

/ L.b SARGENT Q LUNDY ENGINEERS S S E AST MON ROE STR EET CHIC AGO. ILLINOIS 60603 TELEPH ON E 312 2 6 C.2 0 00 May 15, 1931 Project Nos. 4266/67-02 l Commonwealth Edison Company l,, LaSalle County Station - Units 1&2 \\. Flashing in ECCS Suction Line Mr. T. E. Watts i General Design'sauf -sr Conmonwealth Edison Company P. O. Box 767 - 35FNW Chicago, IL 60690o ('

Dear Mr. Watts:

In order to close out the issue of possible flashing in ECCS suct' ion lines, the NRC reviewer requested the routing and calculati,ca be submitted. Enclosed is a description of the calculaticu including all assumptions and data required to. perform the calculation. In addition, sheet 6 of analytical RH-07 and sheet 1 of analytical RH-37 are enclosed to supply the "for record" routing of this section of piping. If the NRC wishes to and.t our calculation rather than per-l. forming their own independent check, our calculation is on l file here and they may audit it anytime they wish. If you have any questions, please contact me. Yours very truly,

v. ZWARIQ G. I. Zwarich GIZ:ch Mechanical Engineer Enclosures In duplicate Copies:

L. O. DelGeorge (1/1/0) E. P. Weaver (1/1/0) G. R. Crane (1/1/0) W. G. Schwartz (1/1/0) R. J. Mazza (1/1/0) G. C. Jones (1/1/0) l D. C. Eaan (1/1/0) J. B. Gouvas (1/1/0) le 4.5 (1/1/1) l O

t Check for Flashing in ECCS Suction Lines Flashing occurs when the vapor pressure of the liquid is equal to or greater than the static pressure of the liquid at that point. To determine if flashing can occur in any of the ECCS suction lines a calculation was performed to determine the local static pressure at the highest elbow located the greatest distance from the suppression pool in the ECCS suction line with the longest equivalent length (LPCI suction line B). First, the total pressure in the elbow is determined, then the dynamic pressure is subtracted to find the static pressure. The following data and assumptions were used in the calculations. Pool temperature ll2*F Minimum pool water level 699.54' (l.ased on low water level alarm minus instrument accuracy) Pump maximum flow 8400 ppm (based on system resistance with all valves wide open for inje.ction.and spray) Schedule 40 Pipe-Strainer 50% plugged has loss of 1.6 psid (manufacturers data) Pipe routing as shown on the attached "for record" analytical drawings 1 psi @ 212' = 2.407' of water (conversion factor) Suppression pool at atmospheric pressure (14.7 psig) The total pressure (H,) at the elbow is equal to the atmospheric pressure plus the head of water minus the permanent flow losses in the strainer and piping. 1.6 (2.407)-1.2' E = 14.7 (2.407) + (699.54-681.17) t H = 35.4 + 18.4 - 3.9 - 1.2 t H t The dynamic pressure (H ) in the elbow consists of two parts. D First the average velocity head and second the difference in ) pressure from the inside of the elbow to the center of the elbow due to the change in direccion of fluid flow through the elbow. H + E D 2g . IR + 0.5 H = D H D --,-w--+ s - =,. - -. +---se ,y w - - - + g-y- -- = <

e e e The static pressure (H ) is the total pressure minus the dynamic g pressure. s H H H = g T D 48.7 - 1.2 H = e g 47.5' H = g Since the vapor pressure of water at 212*F is only 35.4' no flashing can occur. e e e e e 4 e e O e e e e [ i e r, e w.- ~. -nr.m.. -n-, --w---,n--e - - - - -,, - - -, - +.. -, - - - - - - - -w-n,e

h b _g manca 7 _ a. . m w e 9-5 5 @it ot BB 9 .Q ~ f -{lRHolBB-24 T , '3-66) ' w-e ,o, g%h' -- h sf-8'SRELL 5 a u// n eei e [Abh/sh MY$2)=1. .J e rir;z.osoia l nua.uagg /,..o! C 6.iii' 7.772.' 2.ii7 ' m p =

== = 0 -@ EL L1 cay *-

  • a e

e t. 67c.79 2-

==

2 P L A N-A SECTION 'A-A, p g 'G r"'"' x ~. _\\ G i f hx X i My coNTAlNPIENT EGG. (NORTl l DWG. NO. R&V DWG. NO REV. DWG NO MEV DWG NO. REV DwG NO REV ' - ~ ~ - - - - - ~ - - - - My susiv-aztATso M B39 5:i 6 I-90s sapan CI A5147sCAnw]dNoscats2 @RH37 M-96 Sa 2 L LL Q OW L DRAWINGS see riesses ines inst, l JTv. DATE EP ARED CHECK NG. APP L. RE V. DE SCRIPT 40N f at $A ron RE51 DUAL.tiEAI_RErdQEL.PIPINCa_ SYSTEM lmmiumf I _E S4-09-73 d[r

  • ( **(h

%.J Ek% WhnE1EE M1 -l. racaecT_L/L 5ALLE_LOUNT_V i il AT .' ) h 04-50 80 ;/-, @ s 3, ~ ~ 3,,.. [ jTg63,gng i}' -/ 598 SYSTEM NO. REV. @b. Ge...{i__ gg;u ne g_,m , _ 4- + wil, 4 14 o o LynLAw3ogn a.., go. ce sey< R ag i ctiENT.COMMOMEALIlLEDISON CO c c s-i9-,e c..oaau tm M-1041-37 b Q{ D 8-2 4 -1 B 8 t$ PATpt_ ja[;), g_ ro " Mau e % S* S PaOJECT NO. . _ _SHEETj OF 3 i p 3 - r. -w e mi J _ 9e rqr mm T'/ fi6-001 l l i l s l l

O C [lE l2 F 00 + B} d h-100* ELB0W \\ 1 ~~ CU T 70 Sulf '.. - c out OM RH-ST _Ch 8 h/ [ (E., GRHOG AB - 3 ) dlE12F36 M \\ A lla-4 Ol1G lC* Y-SKEW -{I Ell-F3108 ] 6 gg )$y p 343) pck Ho t - 40 H l $ D ' 0 0 *" 0553' ( (IRH 50 A-20) g Nl } 7 Q) ~~ w%. o _ y [ 4. g# m FOR COMT Sll /p / a-m 9 e.s s u s-iuu' s llE 12-F 35~6 B} [ 2 _ 5 833' ~ ~~ m e,drsu upsWof k ut & a 4 344 f 7 gpgap y % W t~ A' 'lRH/,8 AB - 1] QT2 - F379 B }- d f D f 4-DIR ~ {, 885'_ , l rho p-so a 3 ls k Y (IRHG 3 A A -2'} Est g 'k SEE H.SG) +4 SG O\\ [ y,

  • ~Y~

(IPH0 4 DB-lo)+,, 5* P y fa% FOR Core T SEE D D 5 j PLAN E SH.5 10 _ __) _9 og IRH-11 (IRHol A8-2 4-) s x"

  • fl3I i

EL. 6'7 512 5' .I S 26 0* _P L AN F F";r,i,y.,ur,;-~ =2 I*** DwG.NO REV DwG NO. REV DwG NO. REV. OwG NO DwG f=d. REV M-36 5.t. 2 P N-83s SH.6 K H. f(,F E. /. t {IrojsA[sgt se Arsoss' 2 rt ??S F N-8+13tt 5 H a Nd scg e I R 44 -07 l HftEASE HECOf40 PIPIM FeitLYTICAL & PHVslCAL DATA aiv om ...,,uo ..v. ao .,,.oo.o ,ua,os. , 'm [dC gg@dj /5I447fl$ FOR RESIDUAL HEAT REMOuL ISARGENT&lDNOV j f r-at-so EM87J D V kff[ [9' 4~.-e-@f^ ' - sysirne i 1O i n a t-is-ai~ ~a vet'anoars ao => ~ l caosiCT _ L A S ALLE COUNTY 1

  • * * ' * ~

e = < = -4 o r ~< a i a COMMOrlWE ALTH EDISON CO. sua sY$W N4 RW et,,gy j --~ ~ O -- PaoJECT NO. ,}}