Date released: 12/27/2019 Download: ML19347E008


LER 81-030/03L-0:on 810309,diesel Generator 2 Would Not Restart After Being Brought to Speed & Tripping,Apparently Due to Overspeed.Caused by Failed Taper Pin & Bent Level in Governor of Diesel.Turbocharger,Taper Pin & Level Replaced
ML19347E009
Person / Time
Site: Beaver Valley
Issue date: 04/06/1981
From: Werling J
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML19347E009 (2)
Forwards LER 81-030/03L-0
ML19347E007
Person / Time
Site: Beaver Valley
Issue date: 04/06/1981
From: Werling J
DUQUESNE LIGHT CO.
To: GRIER B H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML19347E007 (2)