EQB Rdg. File L
FEB 2 51981 Docket No. 50-322 MEMORANDUM FOR: Robert L. Tedesco, Assistant Director for Lice.nsing Division of Licensing FROM:
Vincent S. Noonan, Assistant Director Paterials and Qualifications Engineering Division of Engineering
SUBJECT:
SAFETY EVALUATION REPORT FOR ENVIRONMENTAL QUALIFICATION OF ELECTRICAL EQUIPPENT FOR b d'4/7 SHOREHAM UNIT 1 PER NUREG-0588 k'%g'oer02198 T' %
Plant *.ame: Shoreham Unit 1 1
g Docket No.:.50-322 p/
Licensing Stage: OL Milestone No.:
g Responsible Branch: Licensing Branch No. 1 N
Responsible Project Manager:
J.N. Wilson Requested Completion Date: N/A Review Status: Continuing The enclosed Safety Evaluation Report (SER) was prepared by DE:MQE, Equipment Qualification Branch. This SER relates to the degree to which the environmental qualification program for the electrical equipment.at Shoreham Unit 1 complies with the staff's position described in NUREG-0588.
Original Signed By:
Vincent S. Noonan, Assistant Director Materials and Qualification Ennineering i
Division of Engineering l
Enclosure.
As stated l
cc:
R. Vollmer D. Eisenhut R. Purple l
Z. Rosztoczy P. DiBenedetto l
J. Page j
H. Walker J. Wilson J. Youngblood DE:Eng DEEg DE:M&Qr 1
1
- - PDiBenedeEYo ZRRoi::toYzy VSNo a,n
' ' 2/ 1A /81 2/ 39 / 81 2/ Zrj. /81 l
81081108<33 g
((
UNITED STATES
,w g
NUCLEAR REGULATORY COMMISSION y
E WASHINGTON. D. C. 20555 L-
. /
e
~%,,,.. *#
FEB 2 5 set Docket No. 50-322 NEMORANDL'M FOR:
Robert L. Tedesco, Assistant Director for Licensing Division of Licensing FR0ft:
Vincent S. Noonan, Assistant Director Materials and Qualifications Engineering Division of Engineering
SUBJECT:
SAFETY EVALUATION REPORT FOR ENVIRONMENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT FOR SHOREHAM UNIT 1 PER NUREG-0588 Plant Name: Shoreham Unit i Docket No.: 50-322 Licensing Stage: OL Milestone No.:
Responsible Branch: Licensing Branch No. 1 Responsible Project Manager:
J.N. Wilson Requested Completion Date: N/A Review Status: Continuing The enclosed Sa fety Evaluation Report (SER) was prepared by DE:MQE, Equipment Qualification Branch. This SER relates to the degree to which the environmental qualification program for the electrical equipment at Shoreham Unit I complies with the staff's position described in NUREG-0588.
a eni S idoo n,
ssistant Director Materia s and Qualification Engineering Division of Engineering
Enclosure:
As stated cc:
R. Vollmer D. Eisenhut R. Purple Z. Rosztoczy P. DiBenedetto J. Page H. Walker J. Wilson J. Youngblood
Safety Evalua.2 ton Report For Shoreham Unit 1 Docket No. 50-322 Environmental Qualification Environmental Qualification of Safety Related Electrical Equipment The applicant has committed to provide an environment qualification submittal on May 1,1981, in accordance with NUREG-0588, Category II.
On this basis, the staff has committed to the following schedule for the c-5pletion of this review. During the week of May 16,1981, the staff will audit the applicants environmental qualification docu-mentation. A supplemental SER will be provided on June 10, 1981, based on the results of the audit.
l i
{