j NRC BHDA CONSUMERS POWER COMPANY PARNALL ROAD OFFICE
. JAC KS ON, MI TWX 517-7 87-1987 9-12-75 5 5-05 PM TO-MR J G KEPPLER USNRC 799 ROOSEVELT RD GLEN ELLYN, IL 60137 RE-DOCKET 50-155, DPR-6, BIG ROCK POINT PLANT THIS WIRE IS SUBMITTED TO CONFIRM THE liLEPHONE REPORT FROM D E DE MOOR TO E JORDAN AT 1530 ON 9-12-75.
1 REPORT NO DOCKET-50-155 2A., REPORT DATE - SEPTEM0ER 6",
1975
- 29. OCCURRENCE DATE - APPROXIMATELY JULY 1975 - CLASSIFIED AO ON 9-12-75.
~
3.
s?.CILITY - BIG ROCK POINT PLANT 4.
IDENTIFICATION OF OCCURRENCE - UNAUTHORIZED ADDITION TO EMERGENCY A.C. POWER PANEL PL.
5.
CONDITIONS PRIOR TO OCCURRENCE - POWER OPERATION.
6.
DESCRIPTION OF OCCURRENCE - DURING INSTALLATION OF THE SITE PHYSICAL SECURITY SYSTEM, SECURITY SYSTEM ELECTRICAL EQUIPMENT WAS CONNECTED TO EMERGENCY POWER PANEL BL WITHOUT PROPER REVIEW AND AUTHORIZATION.
7 DESIGNATION OF APPARENT CAUSE OF OCCURRENCE - FAILURE OF ADMINISTRA-TIVE CONTROLS.
8.
ANALYSIS OF OCCURRENCE - THE LOAD ADDED IS A MAXIMUM OF I.25 kVA COMPA4ED TO A TOTAL OUTPUT OF 250 MVA FOR THE EMERGENCY DIESEL GENERATOR AND DOES NOT COMPROMISE THE SAFETY-RELATED PERFORMANCE OF OTHER EQUIPMENT C,0NNECTED TO THIS EFERGENCY SOURCE.
9.
CORRECTIVE ACTION - A PORTION OF THIS LOAD WILL BE REMOVED FROM THE FMERGENCY POWER PANEL BL AND THE PORTION PROPOSED TO BE LEFT PERMAN=
ENTLY ON THIS PANEL WILL BE REVIEWED FOR PROPER DESIGN CONSIDERA.
TIONS.
NOT APPLICABLE.
- 10. FAILURE DATA R ALPH 9 SEWELL NUCLEAR LICENSING ADMINISTRATOR END - DW CC-DIVISION OF REACTOR LICENSING, USNRC C J HARTMAN, BIG ROCK POINT PLANT CORRECTION-ON 24. A90VE, REPORT DATE - SHOULD READ-SEPTEMBER 12, 1975 VIO3096</SC NRC BNDA
\\
f L-Y[ _
~
- -