Text
avfWAGE DA!LY UNis t ctM Lt V L COCKET NO. 50 - 277 UNIT PEACH BOTTOM UNIT 2 OATE OCTOBER 10, 1960 COMPANY PHILADELPHIA ELECTRIC COMPANY W.M.ALDEN i
ENGINEER-IN-CHARGE NUCL E AR SECTION GENER ATION OIVIS ION-NUCL E AR TELEPHONE (215) 841-5022 i
MONTH SEPTEM8ER 1980 l
DAY AVFRAGE DAILY POWER LEVEL DAY AVERAGE DAILY POW ER LEVFL (MWE-NET)
(MWE-NET) i 1
1031 17 1054 2
1043 18 1051 i
3 1040 19 1054 4
1031 20 1056 5
979 21 1057 6
527 22 1055 4
7 759 23 1055 6
991 24 1054 1
4 1062 25 1056 to 1048 26 1059 l
11 1050 27 1062 12 1050 28 1063 13 1042 29 1064 1
14 1045 30 1065 15 1046 16 1053 4
I e0202sc 377
AVENCGE LAILY UNie PunEd Le<tc OOCKET NO. 50 - 276 UNIT PEACH BOTTOM UNIT 3 DATE OCTOBER 10, 1980 COMPANY DHILADELPHIA ELECTRIC COMPANY W.M.ALDEN i
EN G I NE ER -I N-CH AR G E NUCLEAR SECTION GENERATION O! VISION-NUCLE AR l
TELEPHONE (215) 841-5022 l
MONTH SE P T EMB E R 1980 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL j
(MWE-NET)
(MWE-NET) i 1
1047 17 1054 2
1044 18 1055 1
3 1048 19 1056 4
1043 20 1046 1049 21 1045 5
6 1046 22 1045 7
1047 23 1045 4
1050 24 1044 9
1048 25 1043 10 1048 26 1023 11 917 27 893 12 847 28 1052 13 843 29 1051 14 641 30 1026 15 922 16 1049 6
e e
e UNIT SHUTDOWN 5 AND POWtR N600CIIONS DCCKET NO. 50 - 277 UNIT NAME PEACH BOTTOM UNIT 2 DATE OCTCBER 10 1960 REPORT MGNTH SEPTEMBER, 1960 C OMPLET ED BY PHILADE LPHI A ELECTRIC COMPANY W.M.ALDEN ENGINEER-IN-CHARGE NUCLEAR SECTICN GENER ATION D!vl 5 ION-NUCLE AR TELEPHONE (215) 841-5022 l
l l
l l NETHCD OF l LICENSEE 15YSTEMICOMPONENT l C AUSE AND CORRECTIVE l
lTY PE 10UR AT IONlRE ASON15HUTT ING DOWNI EVENT l CODE l CODE l ACTION TO NO.1 OATE l till (HOUR 5Bl (2) l ME AC TOR 836 i REPORT
- 1 145 l (5) l PREVENT RECURRENCE I
I I
I I
1 i
i 1
11 1 600905 1 5 1 000.0 l
H l 4
l NO NE l RC I ZZZZZZ l LOAD DROP FOR CONTROL ROD PATTERN A0JUSIMENT l
l 1 ----- l l
l l
l l
l 1
1 -
1 I
l l
l 1
(1)
(2)
(3)
(4)
F - FORCED REASON METHOD Exhib!T G - INSTRUCTIONS 5-SCHE DUL ED A - EQUIPMENT FAILURE (EXPLAINI I - M A NU AL FOR PREPARATION OF DATA B - MAINTENANCE OR TESI 2 - M A NU AL SCRAM.
ENTRY SHEETS FOR LICENSEE C - REFUELING 3 - AUTOMA TIC SCR AM.
EVENT REPORT (LER)
D - REGULATORY RESTRICTION 4 - OT HE R (EXPLAINI FILE INUREG-0161)
E - OPERATOR TRAINING + LICENSE EXAMINATION F - ADMINISTRATIVE (5)
G - OPER ATIONAL ERROR (EXPL AIN)
H - OTHER(EXPLAINI EXHIBIT I - SAME SOURCE
_ _ =
m_
m. _.._
m UNIT 1-VT';.N! aN: ':wER eEDuC11CNS DOCMET NG. 50 - 276 UNIT NAME PEACH BOTTOM UNIT 3 DaTS OCTORE8 to, 1960 REF06T "LNTe SEPTEMBER, 1960 COMPLETED BY PHI L ADE L PHI A ELECTRIC COMPANY W.M.ALDEN E NG I NE E R-IN-C HAR G E NUCL E AR SECTION GENER ATION O! VISION-NUCL E AR TE L E PHONE (2153 841-5022 l
l t
l
- ETHCD CF l LICENSEE 15YSTEMICOMPONENTI CAU$t AND CORRECTIVE i
livatlSuaATIONiatASDN!!wuTTING 00kN1 EVENT l CODE l f0DE 1
ACTION TO N3.1 Dait I till IHOUR!il 128 l SEaCTCe 431 1 REPORT
- l
- 44) 1 155 l PREVENT RECURRENCE I
I l -----
l l
l l
l l
l l
1 -
1 I
l l
l l
6m G
1 ilI 428 13) 141 F - FOECED 8E a 50N METHOD EXHIbli G - INSTRUCTIONS (222D 5-SCHECUtiD a - ECUIPwsNT F A I L U4 5 IEsptAIN)
). M A NU AL FOR PREPARATION OF DATA i
B - MAINTENANCE OR TEST 2 - M A NU A L SCRAM.
ENTRY SHE E T S F OR LICENSFt i
C - a E F UE L I NG 3 - AUTomA TIC SCRAM.
EVENT REPORT ILER)
D-REGULa10dv RESTRICT!GN 4 - O T HE R (EEPLAIN)
FILE INUEEG-Ol6tl
- a (h(()
E - OPERATON TkAINING + LICENSE ENAMINATION F - ADMINISTRA TIVE (Si i
G - OPERATIONAL ERROR (FEPLAIN) 67 H - OTHERIEXPLAIN)
ENHIBIT I - SAME SOURCE f "i y
07ERATING DATA RLFONT 00CKET NO. 50 - 277 c3 m
OATE OCT08ER 10, 1980
--C
'3 O
U
[k aU-Jg n
COM*LE T ED BY PHILADELPHIA ELECT *IC CCMosNy c
Ji W.M.ALDEN ENGINEER-IN-CHARGE NUCLE AR SECTION GENERATION Olvl5 ION-NUCLEAR T E L E PHONE (215) 841-5022 i
CPERATING STATUS 1
- 1. UNIT MANE s PEACH SOTTON UNIT 2 1 NOTES: THIS UNIT EXPERIENCE 0 t
l l
- 2. R E PORT ING PE RIDO: SEPTEMBER, 1980 l
DNE PowfR REOUCTION l
l l
- 3. LICEN5ED THERMAL POWERIMwTI:
3293 l
1 l
l 4 NAMEPL ATE RATING f GR055 MWEls 1152 I
l l
l S. DESIGN ELECTRICAL RATING INET MwEle 1065 I
I l
l l
- 6. Max!MUN DEPENOASLE CAP ACITY (GROSS MWEls 1098 I
l l
l l
T. MAXIMUM DEPENDABLE CAPACITY INET MWEls 1051 l
l
{
- 6. IF CHANGES OCCUR IN CAPACITY RATINGS IITEMS NUMBER 3 THROUGH 7) SINCE L AST REPORT. GIVE RE 9
8 0 wf R LEVEL TO WHICH RESTRICTED, IF ANY INET MwElt
- 10. REASONS FOR RESTRICTIONS, IF ANY 4
1 i
l THIS MONTH YR-TO-0 ATE CUMULATIVE i
- 11. HOURS IN REPORTING PERIOD 720 6,575 5*,719 J
- 12. NUM9E R '0F HOURS REACTOR WA5 CRITICAL 720 2,678 40,434
- 13. R E ACTOR R ESERVE SHUT 00wN HOURS 0.0 0.0 0.0 14 HOURS GENERATOR DN-LINE 720.0 2,641.3 39,444.1
- 15. UNIT RESERVE SHUT 00NN Houes 0.0 0.0 0.0
- 16. GRCSS THERNAL ENERGY GENERATED IMwHI 2,275,675 7,074,193 113,841,837 IT. GROSS ELECTRICAL ENERGY GENERATED IMwH) 761,640 2,337,020 37,395,250
- 18. NET ELECTRICAL ENERGY GENERATED (Mwwl 734,417 2,209,684 35,825,469
- 19. UNIT SERVICE F ACTOR 100.0 37.4 72.1
- 20. UNIT AVAIL ABILITY e 4C T OR 100.0 37.4 72.1
- 21. U417 C A*AC ITY P ACTOR tuSING MDC NET) 97.1 32.0 62.3
- 22. UN11 CAPaC11Y FACTOR tuSING DER NET) 95.8 31.6 61.5
- 23. UNIT F04C 50 OUTAGE RATE 0.0 2.2 6.I 26 SwuTOOWNS SCHECULED OvFR NEXT 6 MONTHS (TYPE. DATE. AND DUR ATION bF E ACHi t
(
23, 15 5 HUT 00hN AT ENC OF R E POR T PERIOD, ESTIMATED DATE OF STARTUPt 2o. UNITS IN TEST ST AT US (*RIOR TO COMMERCIAL OPERATION):
FOR EC AST ACHIEVED INITIAL CRITICALITY INITIAL E L EC TR IC ITY COMMERCI AL OPER ATION
CEElitliG OITI Ft LA.
00CRET No. 50 - 276 DATE OCTOMER 10, 1960 COMPLETED SV *HILADEL*HIA ELECTRIC Company W.M.ALDEN E NG IN E E R-I N-f H A RG E NUCLEAR SECTION GENERATION O!VI$10N-NUCLE AR T E L E 8HO NE (215) 841-5022 OPER ATING ST ATUS
- 1. UNIT N AME : PEACH BOTTOM UNIT 3
- NOTES: THIS UNIT EXPERIENCE 0 NO I
l l
- 2. R E POR T ING PE RIDO: SEPTEMBER, 1960 l
MAJOR OUT AGES OR MAJOR I
g i
1
- 3. L ICENSED THERMAL POWERIMWTI:
3293 I
POWER R E DUC TI ONS I
l l
4 N AME PL ATE RATING IGROSS MWE l s 1152 1
i i
i j
- 5. D E SIGN EL ECTRICAL RATING INET MWE l s 1065 I
I l
l 6.
M A XIMUM DE PE NOABLE C AP ACITY IGROS$ MWEle 1098 I
l g
i
- 7. M A AINUM DE PENDABLE CAPACITY INET MWEle 103S I
l
- 8. IF CHANGE S OCCUR IN C AP ACITV R ATINGS IITEMS NUMEER 3 THROUGH 71 SINCE LAST RE80RT, GIVE dE A 5C' J
i 9
8 0 WF R LFVE L 10 WHICM RESTRICTED, IF ANY INET MWE):
- 10. R E ASONS 804 RESTRICTIONS, IF ANY:
THIS MONTH YR-TO-0 ATE CUMULATIVE
- 11. MCUR$ IN R EPCRTING PE RICO 720 6,575 50,615
- 12. NumeER OF HOURS REACTOR WAS CRITICAL 720 5,427 40,273
- 13. R E ACTOR RESERVE 3HUTDOWN HOU95 0.0 0.0 0.0 16 MCUR $ GENE R ATOR ON-L INE 720.0 S,258 2 39,190.0
- 15. UNIT 8ESE RVE SHUT 00WN HOURS 0.0 0.0 0.0 4
- 16. Gn C$ $ THE
- MAL ENERGY GENER ATED (MVH1 2,295,010 16,726,292 110,945,446
- 17. Ca CS S ELEC TR IC AL ENERGY GENERATED IMWHI 755,010 5,554,260 36,144,120 lb. Nff ELFCTDICAL ENERGY GFNERATED I M WH) 728,622 9,353,859 34,698,659
- 19. UNIT SERV!CE F ACTOR 100.0 80.0 77.4
- 20. UNIT AVAILAEILITY FACTCR 100.0 80.0 77.4 1
a.
- 7.8 74.7 66.2
- 22. UNIT C ARACITY SACTOR sus!Nr. DER NET) 95.0 76.S 64.4
- 23. UNIT 8 CRC 50 OUTAGE RATE 0.0 12.5 7.6 24 !*0100wNS SCHEDUL ED QWE R NE XT 6 MONTH 5 ( T YP E, D AT E. A NO DUR AT ION OF E ACH l :
25 15 SMUTS 0wN AT END C# REPORT DERIDO, E51!44TED DATE OF ST ARTUP:
?c. ONif 5 IN TEsf $7ATUS 184!04 70 C0=MERCIAL 0*ERATION):
F DR EC AST ACHIEVED INITI AL CRITICALITY INITIAL 8 L EC TR IC ITY CO*mE#CI AL OpER AT ION
.M C tN.
..v.
Attach:ent to Monthly Operating Faper-For September, 1960 REFUELI @ INFORMATION 1.
Name of facility:
Pea.ch Bottom Unit 2 2.
Scheduled date for next refueling shutdown:
January 2, 1982 3
Scheduled date for restart following refueling:
Fobruary 13, 1982 l
h.
Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?
i l
Yes.
If answer is yes, what, in general, will these be?
l Technical Specifications to accommodate reload fuel.
Modifications to reactor core operating limits are expected.
5 Scheduled date(s) for submitting proposed licenair4 action and supporting information:
l November 13, 1981 i
6.
3portant licensing considerations associated with refueling, e.g.,
new or different fuel design or supplier, unreviewed design or j
performance analysis methodt, significant changes in fuel design, new operating procedures:
i 1
None expected.
7 The number of fuel assemblies (a) in the core and (b) in the spent fuel storage pool:
(a) Core - 76h Fuel Assemblies i
I (b) Fuel Pool - 910 A el Assemblies i
l
\\
l l
8.
The present licensed spent fuel pool storage capacity and the size of any increase in licensed storage capacity that has been requested or is planned, in number of fuel assemblies:
The spent fuel pool stcrage capacity has been relicensed for 2816 fuel assemblies.
9 The projected date of the last refueling that can be discharged to the spent fuel pool assuring the present licensed capacity.
September, 1990
Docket ;;o. LO _.c Attachosnt to Monthly Operating Repcrt For September, 19_0 REFUELING INFORMATIUN 1.
Name of facility:
Peach Bottcm Unit 3 2.
Scheduled date for next refueling shutdown:
March 7, 1981 3
Scheduled dato for restart fol;owing refuelir4:
Juno 27, 1981 h.
Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?
Yes.
If answer is yes, what, in general, will these be?
Technical specification changes to accommodate reload fuel.
Modifications to reactor core operating limits are expected.
5.
Scheduled date(s) for submitting proposed licensing action and supporting information:
March 6, 1981 6.
Important licensing considerations associated with refueling, e.g.,
new or different fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new operating procedures:
None expected.
7 The number of fuel assemblies (a) in the core and (b) in the apent fuel storage pool:
(a) Core - 76h Fuel Assemblies (b) Fuel Pool - 712 IIradiated Fuel Assemblies 1
8.
The present licensed spent Iuel pool storage capacity and the size of any increase in licensed storage capacity that has been requested or is planned, in number of fuel assemblies:
The spent fuel pool stcrage capacity has been relicensed for 2816 fuel assemblies.
9 The projected date of the last refueling that can be discharged to the spent fuel pool assumirg the present licensed capacity:
September, 1991
O PEACH 30TTOM ATOMIC IGi:R STATION NARRATIVE SUNY OF OPERATING EXPERIENCES SEPTEMBER. '980 UNIT 2 OPEPdTIONS On September 14, the Unit experienced a 30 megawatt reduction due to inaccuracies in the core flow instrumentation. On September 5, a load reduction was taken to adjust the control rod pattern. The i
Unit returned to full power on September 8 via a preconditionirs ramp.
l The High Pressure Core Injection system was out of service from September 10 to September 11 to accommodate repairs to its turbine exhaust rupturo disc. The RCIC system was out of service on September 12 to accommodate replacement of the ther=al overloads for the RCIC turbine inboard steam supply valve. The "B" control rod drive pump was out of service from September 6 to September 17 due to a bearing failure.
UNIT 3 OPERATIONS On September 11 load was reduced to approvientely 800 megawatt to accommodato repair of the "B" condensate pump shaft sleovo and throttle bushing. T5 was also repa d and the Unit was returned to full po,
. Jepte=ber 15 aeen September 25 and 30, two load reductions were taken to ir. A tigate condenser leaks.
The Unit was returned to full power on September 30 with the 3-2 water box out of service, b
l
~
-