ML19345E459
| ML19345E459 | |
| Person / Time | |
|---|---|
| Site: | Big Rock Point File:Consumers Energy icon.png |
| Issue date: | 08/24/1967 |
| From: | Worthington J GENERAL ELECTRIC CO. |
| To: | James Shea US ATOMIC ENERGY COMMISSION (AEC) |
| References | |
| NUDOCS 8101190422 | |
| Download: ML19345E459 (2) | |
Text
..
/
d
}
i
- . 4. u-.
s
, //RP#
goyfs TVX NO 86 Righiatory suppt File Cy._
910-35E-0l!6 SAN JOSE CALIF 8/24/67 J J SHEA* USAEC DIVISION OF REACTOR LICENSING BETHESDA MARYLAND THE FOLLOWING WUMBERS ARE THE RESULTS OF A 2 PUMP TRIP FROM
' RATED POWER FOR BRP.
POWER AND FLOW IN PERCENT OF RATED.
TIME POWER CORE McHFR MCHFR
/SEC./
FLOV
/CENTT. MELT /
/ AVG.11X11/
0 100 100 1.98 3.47 1
89 67 2.22 3.89
~
2 77 52 2.57 4.50 3
68 45 2.91 5.10 4
61 43 3.24 5.68 CENTERMELT ANALYSIS APPLIES TO 7X7 AND EX8.
C FUEL IS FOR AN AVERAGE ASSEMELY BUT PEAK OR MOST LIMITING ASSEMBLY WOULD BEHAVE THE SAME W AY WITH MCHFR ALWAYS RISING.
ORIGINAL SENT TO J J SHEA USAEC BETHESDA MARYLAND' COPY TO R L HAUETER' CONSUMERS POWER C0 JACKSON MICHIGAN.
J T WORTHINGTON, GENERAL ELECTRIC CO gg16 END:
PLS ACK u..e
_c m..
u.
L.
m 5
l l 7/bll94feA
,