e,

(

CONSUMERS POWER COMPANY 1964 t,UG 7

/l 0 So, PARNELL ROAD OFFICE JACKSON, MICHIGAN U.S. ATCMi i

^j ' CC;'.1 T Y.' X 'J.. i AUGUST 7, 1964 B W 3 %. & d4 T~.

TO - DR. R. L. DOAN, DIRECTOR Y

pq O Copg /

DIVISION OF REACTOR LICENSING Y

c:

UNITED STATES ATOMIC EMERGY COMMISSI "

P 5

D y,$'

I' WASHINGTON, D.C.

O s 11 00Cgg i g ':

4 b g g

b ATTENTION - MR. JAMES SHEA !

gg g 7 _ -.

q b

v o>

w THE FOLLOWING INFORMATION REGARDING THE BIG ROCK POINT REACTOR, DOCKET 50- 155, IS HEREBY SUBMITTED IN ACCORDANCE WITH THE REC' JEST BY YOUR STAFF -

FOR THE 44-BUNDLE CORE - POWER LEVEL 165 MWT,, TOTAL RECIRCULATION FLOW 11,',00.,000 LB/HR, BYPASS LEAKAGE'22.2 PERCENT, PLENUM TO PLENUM DELTA ' P ?2.45 PSI, AVG CHANNEL FLOW 203,000 LB/HR, HOT CHANNEL FLOW 200,000 LB/HR.

FOR TPE 56-BUNDLE CORE - POWER LEVEL 157 MWT, TOTAL RECIh.ULATION

. FLOW 12,400,000 LB/HR, BYPASS LEAKAGE 21.0 PERCENT, PLENUM TO PLENUM, DELTAP8.64 PSI,AVCCHANNELFLOW1h5,000LB/HR,H0i CHANNEL FLOW 150,000 LB/HR.

[/p// h p C[p

l l

P 1

[_

.31.

m.

u

[

5R. T9E 84-BUNDLE ( IE - POWER LEVEL 240 MUT,

.TAL RECIRCULATION 12,500,000 LB/HR, BYPASS LEAKAGE 20.1 PERCENT, PLENUM TO PLENUM DELTA P 5.84 PSI, AVG CHANNEL FLOW 132,500 LB/HR

--NOTE -

AVG OF ALL BUNDLES IN STANDARD ORIFICE REGION.

INCLUDING THE SMALL

~

PERIPHERAL ORIFICE REGION, THE AVG WOULD BE 119,000 LB/HR-,

HOT CHANNEL FLOW 122,000 LB/HR.

ROBERT L. HAUETER s

ASSISTANT ELECTRIC PRODUCTION SUPERINTENDENT - NUCLEAR END WL F55 AM 07/14552 AUG DV YE 4095

-._..3 6