ML19344F002
| ML19344F002 | |
| Person / Time | |
|---|---|
| Site: | Atlantic Nuclear Power Plant |
| Issue date: | 08/27/1980 |
| From: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| To: | Collier A OFFSHORE POWER SYSTEMS (SUBS. OF WESTINGHOUSE ELECTRI |
| References | |
| NUDOCS 8009120248 | |
| Download: ML19344F002 (1) | |
Text
U f.
p ner
/
t"4 UNITED STATES 8"
NUCLEAR REGULATORY COMMISSION E
REGION Il 4
101 MARIETTA ST., N.W., SUITE 3100 e,
s ATLANTA, GEORGIA 303o3 AUG 2 71980 In Reply Refer To:
RII:JPO Q0437)
Offshore Power Systems ATTN:
A. R. Collier, President P. O. Box 8000 Jacksonville, FL 32211 Gentlemen:
This Information Notice is provided as a notification of a matter of possible safety significance. It is expected that recipients will review the infor aation for possible applicability to their facilities, and where applicable, consider the recommended action. If you have questions regarding this matter, please contact the director of this office.
Sincerely,
.Q ames P. O'Reilly
" rector
Enclosures:
1.
IE Information Notic No. 80-31 l
2.
List of Recently Issue
_ T ation Notices
(
l l
l t
l 6009120.fYI Q
SSINS No.: 6870 Accession No.j D 8006190040 p '7 IN 80-31 o
UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGT3N, D.C. 20555 August 27, 1980 IE Information Notice No. 80-31: MALOPERATION OF GOULD-BROWN BOVERI 480 VOLT-TYPE K-600S AND K-DON 600S CIRCUIT BREAKERS l
Description of Circumstances:
The Cincinnati Gas & Electric Company reported problems with the Gould-Brown j
Boveri Type K-600S and K-DON 600S circuit breakers used in 480 volt a.c.
circuits at the William H. Zimmer nuclear stations. The problem involved inadvertent circuit breaker closure during operation of the breaker charging springs when the breaker was racked out to the test position.
The problem resulted from the use of undersized bushings in the circuit breaker secondary close latches. The undersized bushings caused the secondary close latch to hang-up on the shunt trip device resulting in an inadvertent circuit breaker closure when the spring charging motor was energized.
The vendor has stated : hat the problem does not exist during normal operations with the circuit breakir in the connected position.
Recommended Action for '.icensees and Holders of Construction Permits:
All licensees of operatiag nuclear power reactors and holders of construction permits should be aware of the potential problems described above. The vendor has stated that a small number of circuit breakers were assembled with under-sized secondary latch bushings between 1969 and 1977.
It is recommended that the following actions be taken:
(1) Determine if the subject circuit breakers are installed in any safety-related application at your facility. The affected circuit breakers are manufactured by Gould-Brown Boveri and are types K-600S and K-DON 600S, 480-volt a.c. electrically operated, drawout type with static trip device.
(2) If it is determined that your facility has the circuit breakers described in Item (1) above, perform the K-600S, K-DON 6005 Field Test Procedure attached to this information notice (Gould-Brown Boveri I.B.-9.1.7-6 Issue F, Addendum 2, dated March 4, 1980).
(3) If maloperation of the circuit breaker occurs during performance of the field test procedure described in Item (2) above, perform the corrective action described in the attached stallation of a 0.050 shim to the secondary clos DUPLICATE DOCUMENT Entire document previously entered into system under: