Responds to NRC Re Violations Noted in IE Insp Rept 50-482/80-12.Corrective Actions:Fire Fighting Provisions Made,Reactor Refueling Area Assigned Zone Designation & Access Controls Established
ML19344E289
Person / Time
Site: Wolf Creek 
Issue date: 07/22/1980
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML19344E287 List:
References
NUDOCS 8008280328
Download: ML19344E289 (3)


Text

f "N g

-- - - meme co.-v GLENN L. MQESTER veCE potasotset.catearecess July 22, 1980 Mr. W.C. Seidle, Chief Reactor Construction and Engineering Support Branch U.S. Nuclear Regulatory Connission Region IV 611 Ryan Plaza Drive Suite 1000 Arlington, Texas 76011 IC1LNRC-014 Re: NRC Docket No. STN 50-482/Rpt. 80-12

Dear Mr. Seidle:

This letter is written in response to your letter of June 19, 1980, which transmitted Inspection Report 50-482/80-12.

As requested, each finding 4s being addressed in three parts:

a)

Corrective steps which have been taken and the results achieved; b)

Corrective steps which have been taken to avoid further noncompliance; and c)

The date when full compliance will be achieved.

Finding 1.

No provisions for fire fighting involving the use of an available connunity fire department have been made as of June 10, 1980, in applicable procedures or instructions.

2.

Trained fire brigades are not used in that:

a.

Practice drilling of the existing site fire brigade has not been done on a regular basis.

b.

Fire brigade training sessions have had an inconsistent attendance.

c.

In addition, site fire brigades have not been assigned to the three day weekend shift or to the night shifts as of June 10, 1980.

soossso 329 201 N. Market - Wichsta. Kansas - Mad Address: P.O. Box 208 i Wrchsta. Kansas 67201 - Telephone: Area Code (316) 261-6451

e Mr. W.C. Seidle D CIRC-014 July 22, 1980 3.

Fire fighting instractions and planning for evacuation of personnel from confined areas do not exist.

Response

a) he Burlingten Rural Fire Cepartment has been contacted.

Their full cooperation and support in fighting a fire which

=ight occur at Wolf Creek was assured.

Instractions for contacting the Burlington Rural Fire Iepartment will be incorporated into Procedure AP-XIII-03.

Fire brigades have been established for each working shift, including night shifts and the weekend shifts. Training /

practice sessions are being conducted for all brigades and will be centinued en a regular basis.

Doc =:nentatien of each training session including a list of attendees will be

..aintained.

The censistency of personnel assigned *w each brigade will be maintained to the extent practical within the constraints imposed by changing work assignmen*a, changing shift assignments and personnel turncver.

Curing the period June 18-28, 1980, six training sessions were conducted involving righty fire brigade members.

Fire fighting instructions and c evacuation procedure for persennel working in remote locations have been developed and will be issued as a part of ProceCre AP-XIII-03.

b)

The Project Safety F.ngineer has e@hasized to the safety supervisory persennel the i=portance of strict ecq11ance with the requirements which will be included in AP-XIII-03.

Documentation required per AP-XIII-03 will be =aintained on site for NRC review.

I c)

Full compliance will be achieved on or before Septe=ber 5, 1950.

i i

Findine l

Cn June 6,1980, a specific ene designation (Zene I, II or III), in ce=pliance with A';SI N45.2.3 and associated cleanliness requirements ce=-

mensurate with the current constructicn setivities, had not been assigned or i=plemented by the constraction =anager for the reactor refueling cavity in the Containment Building. The refueling cavity was open for work en the installed reactor vessel during the morning of June 6, 1980.

he reac*ar internals are also stored in the rear':cr refueling cavity.

Resocnse a)

At the present time the reacter vessel is e=pty; that is, the internals have not yet been installed. They are covered and

e Mr. W.C. Seidle KMLNRC-014 July 22, 1980 stored in the refueling cavity. Therefore, all parts of the primary system are still accessible.rnd the material accounta-bility required by ANSI N45.2.3 Zone III is not yet needed.

However, control of personnel entering the cavity and the pro-hibition against the entrance of food or tobacco as required by Zone III is appropriate. Accordingly, the area has been desig-nated Zone IV with an additional provision for controlling personnel access.

A security guard has been stationed at the entrance to the cavity so as to allow only persons whose name appears on the authorized entry list to enter the cavity.

  • When the guard is not present the entrance is locked.

b.

To clearly establish the above controls, which are in force, procedure AP-XIII-05 " Project Housekeeping" is being revised, c.

Procedure AP-XIII-05 will be revised and issued by August 15, 1980.

Please advise if you need additional information.

Yours very truly,