Ro:During Period 801020-1112,diesel-driven Fire Pump Will Be Inoperable During Planned Maint Overhaul.Local Fire District Will Station Pumper Truck at Site During Outage.Rept Forwarded Per Limiting Condition of Operation in Tech Specs
ML19344B512
Person / Time
Site: Trojan File:Portland General Electric icon.png
Issue date: 10/16/1980
From: Yundt C
PORTLAND GENERAL ELECTRIC CO.
To: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
CPY-1023-80, NUDOCS 8010210385
Download: ML19344B512 (1)


Text

.

A e

+

'f l

M M

r "E @

Portland General E!cctric Company Trojan Nuclear Plant P.O. Box 439 Rainier, Oregon 97048 October 16, 1980 l

(503)556-3713 CPY-1023-80 l

Mr. R. H. Engelken, Director l

US Nuclear Regulatory Commission, Region V l

'1990 North California Soulevard i

Walnut Creek, California 94596 l

Dear Sir:

A Limiting Condition for Operation (LCO), 3.7.8.1 of the Trojan Technical Specifications, requirer that a special report be provided in the event of i

inoperability of the fire suppression system. System operability as de-fined by Paragraph B of the referenced LCO will not be met during a planned maintenance overhaul of the diesel-driven fire pump. The inspection in-cludes preventative maintenance on the diesel engine as well as the pump.

l In addition, the pump also will be coated with a corrosion inhibitor at l

this time. This letter represents the initial notification and follow-up l

report as required by the Technical Specifications.

The removal of the diesel-driven fire pump requires that an additional source of fire suppression water be provided as a backup to the electric motor-driven fire pump. The Rainier Rural Fire Protection District has agreed to station a pumper truck at the site while the diesel-driven pump is out of service. A drafting connection from the cooling tower basin will l_

provide the necessary pumper water supply. The pumper will be aligned to discharge into the fire main via Hydrant No. 3 located south of the Secu-rity Bu12 ding. The pumpe~ will only be used in the event of an electric motor-driven fire pump failure. It is anticipated that the system will be in this cot 4 figuration from October 20 through November 12, 1980.