ML19344B199

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 80-16.Rosemount,Inc Model 1152 Transmitters W/Output Codes a or D Identified in Reactor Heat Removal & Core Isolation Cooling Sys.Amplifier Boards of Affected Transmitters Will Be Replaced by 810101
ML19344B199
Person / Time
Site: Perry  
Issue date: 08/11/1980
From: Davidson D
CLEVELAND ELECTRIC ILLUMINATING CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
IEB-80-16, NUDOCS 8008250734
Download: ML19344B199 (1)


Text

.'

  • .v, c

ILLU*.tlNAT* 4 SLOG e PUBUC Set,, art e s!LE'.[LA %Q dt.to 4.'. e it LP**0Na.2't4 6231150 e *'AL A.

-f55 P. o. B o A 8000 w(t

. :p Tr:e da.:.

m :~e Nnos Ca!w,n R. Davicson e:t ut s ces:

s.r w ese,+.st e.a 4.: :;.r%:r:cs August 11, 1980 Mr. James G. Kepp'.ar, Director Region III Office of Inspection and Enforcement U. S. Nuclerr Regulatory Commission Glen Ellyn, Illinois 60137 Re: Perry Nuclear Power Plant Docket Nos. 50-440, 50-441

. Construction Permit Nos.

CPPR-148, CPPR-149 IE Sulletin No. 80-16

Dear Mr. Keppler:

In accordance with your request, the following information is provided in response to IE Bulletin No. 80-16.

All Rosemont Model 1152 Pressure Transmitters supplied for the Perry Plant have been identified. Tnose transmitters procured directly from Rosemont have "E" output codes, and are not affected under this bulletin. Our NSSS supplier has identified Model 1152 pressure transmitters with output codes "A" or "D" in the Reactor Heat Removal and Reactor Core Isolation Cooling Systems. The amplifier boards of all affected transmitters will be replaced with new "E" boards, per Rosemont's recommendation.

Corrective action will begin in September and replacement should be coeplete by January 1, 1981.

This information was provided as a potential significant deficiency in our letter dated June 30, 1980.

If you require additional information, please let me know.

Very truly yours,

/g a

Dalwyn R. Davidson Vice~ President DRD:kas System Engineering and Construction U. S. Nuclear Regulatory Commission cc:

Office of Inspection and Enforcement Division of Reactor Construction Inspection k'ashington, DC 20555 dO!

3 U. S. Nuclear Regulatory Commission c/o Document Management Branch hI 8 k'ashingten, DC 20555 8008250=f34