I N Commonwrith Edis:n O ) One Drst Nabonal Plaza. Chicago. Ithnois O

Address Repli to ' Post Olkce Box 767 Chicago, Illinois 60690 December 19, 1980 1

Mr. Harold R. Denton, Director Of fice of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, DC 20555 4

]

Subject:

Zion Station Units 1 and'2 Additional Information on Station Electric Distribution System Voltages r

NRC Docket Nos. 50-295 and 50-304 References (a):

May 2, 1980 letter from S.

A.

Varga to D. L.

Peoples 1

(b):

June 23, 1980 letter from W. F..Naughton to H.

R.

Denton i

Dear Mr. Denton:

l l

This is to provide additional information regarding Commonwealth Edison's response (reference b) to.NRC questions on i

adequacy of station electric distribution system voltages (reference c).

' of reference (b) indicates station electric distribution system voltages when the ESF bus of one unit is

.i operated from the second offsite power supply via a 4 kv bus J

crosstle.

This'is an unusual arrangement and is used only when at cold shutdown in accordance with plant operating procedures.

Also, i

as noted on Attachment 3, start of-the 11,000 horsepower steam i

generator feedwater pump is not permitted in this configuration.

The low voltage condition (69.1%) on 480 volt bus 138 was therefore computed using'an excessively conservative set of acsumptions'and should not be considered to be a design basis. case.

1 Please-address-any further. questions to.my: office.

S One-(1 signed original and thirty-nine (39) copies of this ytransmitt'ahare)provided'foryouruse.

=

Et f.

((

U g

Very truly yours,

} l( f.Adevn b

J:

T. R.

Tramm o

Nuclear-Licensing Administrator b

Pressurized Water Reactors