g N

s!

O I'

' Appendix A

' NOTICE OF VIOLATION Commonwealth Edison Company Docket No.50-010 ; 50-237; 50-249 T,ased on the inspection conducted on Apri'. 20-?2, 25, and 27-29, and May 6 and 13, 1977, certain of your acaivities appear to have been in noncompliance with NRC requirements, as noted below.

All three items are infractions.

- 1.

Contrary to Technical Specification 3.8.A.2.b, releases of halogens and particulates (w1.' half-lives longer than eight days) from the station exceeded the release rate limit during the period April 15 at 0930 hours0.0108 days <br />0.258 hours <br />0.00154 weeks <br />3.53865e-4 months <br /> to April 16, 1977, at 1400 hours0.0162 days <br />0.389 hours <br />0.00231 weeks <br />5.327e-4 months <br />.

2.

Contrary to Technical Specification 6.6.B.1, releases of

'nalogens and particulates (with half-lives longer than eight days) exceeding the release rate limit (a limit-ing condition for operation) during the period April 15 at 0930 hours0.0108 days <br />0.258 hours <br />0.00154 weeks <br />3.53865e-4 months <br /> to April 16, 1977, at 1400 hours0.0162 days <br />0.389 hours <br />0.00231 weeks <br />5.327e-4 months <br /> were not reported to the NRC until April 22, 1977, a period of time, greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

3.

Contrary to Technical Specification 4.7.B.1, monthly operational tests of the Standby Gas Treatment System were not perfo,rmed during February and March 1977.

e e

8009030 h2 N

.