Responds to IE Bulletin 80-17,Suppl 3.Outlines Procedures in Effect Re Loss of Instrument Air,Loss of Control Rod Driveline,Rod Drift & Undrained Scram Discharge Vol.Function Test of Switches Required Prior to Startup
ML19338E040
Person / Time
Site: Hatch  
Issue date: 08/29/1980
From: Widner W
GEORGIA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-80-17, NUDOCS 8009240367
Download: ML19338E040 (2)


Text

.

-,......m~m-~~--<

, m. 2c_ _

= : a.u. ;

1.

J

. ~

l Georg5 Power'Cornpany ?

/

' 230 Peacntree Street E '

.Li i Post Offee Boi 4545

! j{ '

f-

~ Atlanta Georgia 30302, LTeicphone 404 522 606o U S M R O R E GI,. g '..

/,Ttt,NT/. F F '

L

w. A. w%,..

,0 SEP2 - All : 33 GeorgiaPbwer ge Pres dent and General Manager V

August 29, 1980 U. S. Nuclear. Regulatory Commission'

-Office of' Inspection and-Enforcement

. Region II

. Suite 3100

~

REFERENCE:

RII:

.0,

101 Marietta Street, NW ~

-321/50-366 D Atlanta, Georgia 30303 I&E Bulletin 80 ;

" ATTENTION: Mr. James P.LO'Reilly

~

GENTLEMEN:

t The following information is submitted in response to I&E Bulletin 80-17, Supplement 3.

-Regarding Item 1 of the Bull are.an integral part of the scrametin, the instrument volumes 'on Unit 2 discharge volume; therefore, this item is not applicable. Unit 1 'does have 2-inch piping connecting the instrument volume-and the SDV; however,-the hi-level (scram) switches are connected directly to the SDV. 'Therefore,' the concern of this item is not applicable.

. At present, the following procedures concerning Supplement 3 are in

'effect:at Plant. Hatch:

g 1.

HNP-1-1920 Loss of-Instrument Air Plant service air is isolated at.70 psig decreasing.

Nonessential r

instrument air is isolated:if the pressure drops-below 50 psig.

4 Essential: instrument air does not isolate.

If the-recovery of' the air supply is not possible-immediately, then the reactor is manually scrammed.- The CRD system uses L

essential instrument air and is annunicated at 70 psig decreasing air pressure.

I 2.

-HNP-1-1940 Loss of CRD' System This' procedure-requires that'if two or more CRD's indicate high temperature alarms annunciate, then the ~ CRD drive temperatures are_ monitored closely, and all drives that' exceed 4000F are scram time tested.

3.

HNP-1-2424 Rod Drift.

If an alarm is_ received' indicating that a control rod has drifted

~

'from its latched position'and the cause of' drifting cannot be corrected, then the rod is fully inserted and electrically disarmed.

9 Also required is that reactor.. engineering be notified to determine.

lwhether a. limiting control rod pattern exists.

4 1

80.0924 0 8 6T-

' OFFICIAL COPY

(

n

,7 3

GeorgiaPbwerA U. S. Nuclear; Regulatory Commission Office.of Inspection and Enforcement August 29, 1980 Page Two 4.--

HNP-1-2409 SDV Not-Drained

~

If an alarm is received in the control room indicating that the.SDV is not empty due to either a post-scram draining or due to leakage accumulation, the following-steps are to be taken:

-a.

Check that the SDV drain and vent valves are open.

b.

Check for partially open scram discharge valves if a full scram-is not present.

c.

Observe rod display panels for drifting rods.

~d.

Check the individual CRD module SDV lines 'or abnormally high f

temperatures.

In accordance with Item 2 of the Bulletin, a standing order has been issued requiring a functional test of all 6 level switches (scram and rod block) prior to startup following a scram on either unit.

.Please contact this office if you need additional information in this regard.

Sincerely, 7s:d.2/ b' 1

W. A. Widner REB /mb

-Sworn to and subscribed before me this 29th day of August, 1980.

Notary PGblic, Georgia, State at Large

[L h(

M: /]/,

Wcommission Leires sept.29,1981 i

Q

' Notary Public Jc:

Director of the Office.of Inspection and Enforcement

~ Director of the Division of-Operating Reactors, Office of

- Nuclear Reactor Regulation 1

i

'