ML19338D765

From kanterella
Jump to navigation Jump to search
Forwards LER 80-057/03L-0
Date released: 12/18/2019 Download: ML19338D765


LER 80-057/03L-0:on 800821,fluid Drive Pump Tripped & Backup & Emergency Oil Pump Did Not Start.Caused by Coil Burnout on 125 Volt DC Agastat Relay Model #2412.Relay Replaced & Design Change Initiated
ML19338D775
Person / Time
Site: Pilgrim
Issue date: 09/19/1980
From: Marjorie Mclaughlin, Mcloughlin M
BOSTON EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML19338D775 (1)
Forwards LER 80-057/03L-0
ML19338D764
Person / Time
Site: Pilgrim
Issue date: 09/19/1980
From: Machon R
BOSTON EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML19338D764 (1)