Responds to NRC Re Violations Noted in IE Insp Repts 50-348/80-03 & 50-364/80-03.Corrective Actions: Misplaced Sprinkler Heads to Be Relocated & Hot Shutdown Panel Under Const to Allow Safe Shutdown
ML19338C339
Person / Time
Site: Farley  
Issue date: 07/21/1980
From: Clayton F
ALABAMA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19338C338 List:
References
NUDOCS 8008150165
Download: ML19338C339 (5)


Text

M WY 600 North 18th strost 6

Post Office Box 2641 I

Birmingham, Alabims 35291 e

Tslaphone 205 323-5341

)

'j'.;;iil O R E O n t? !.

T! t fit /.. C: ' " ' ' -

h hko?'C'sii Alabama Power July 21.,3 M 30 All: 46 1

Docket No. 50-348 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Comission Region II 101 Marietta Street N. W.

Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

i Enclosed for your review is Alabama Power Company's response to the fire protection inspection conducted by Mr. W. H. Miller, Jr., on February 26-29, 1980.

If you have any questions or desire additional information, please advise.

i Yours very truly, k

bb F. L. Clayto Jr.

JDM/rt Enclosure cc: Mr. R. A. Thomas Mr. G. F. Trowbridge Mr. W. H. Bradford Mr. E. Reeves l

l l

U FICIAL COPY 8 0080150 %$

i ENCLOSURE The following is a listing of open items as reported in Mr. W. H. Miller's Inspection Report dated March 24, 1980.

It should be noted that the bulk of the open items deal with portions of the fire protection system which, based on Mr. Miller's inspection, do not meet the provisions of National Fire Pro-tection Standard No.13 and Standard No.15. As noted in Mr. Miller's report:

"Section 4.1 (Table 4.1.1 Item E.3.(c)) of the FPPR states in part that the automatic sprinkler systems at the facility cor. ply with the provisions of National Fire Protection Association Standard No.13 (NFPA-13), Sprinkler Systems, and Standard No.15 (NFPA-15),

Water Spray Systems."

APC0's intent in applying the applicable portions of these standards was to invoke such criteria where applicable to a nuclear plant and where they provide adequate fire suppression capability.

Where implementation of certain portions of these standards was unfeasible due to existing plant confirguration, APC0 developed a fire protection scheme, unique to each situation which provides equivalent, or in some cases better, fire suppression capability than would have been provided by strict adherence to NFPA codes.

With this understanding, the open items are stated as they appear in Mr. Miller's report together with Alabama Power Company's (APCO) response.

Item 5.a (1):

Automatic Sprinkler Systems (a) Many portions of the sprinkler protected areas contain from minor to serious obstructions to the discharge of water in the event of fire.

This is due to sprinkler heads (discharge nozzles) being obstructed by electrical and mechanical equipment and components and by structural beams and supports as a result of-the design and/or installation of the systems and as a result, does not fully meet the provision of Sections 4-2.3, 4-2.4, 4-3 or 4-4 of NFPA-13.

In general, sprinkler heads must be positioned to compensate for obstructions or additional heads 'must be provided.

(b) Sprinkler heads are installed below the ceiling / roof of structures at a greater distance than that permitted by the provisions of Section 4-3 of NFPA-13.

Response

APC0 had performed sprinkler system walkdowns prior to the audit and was aware that existing plant configuration did not constitute strict adherence to the code provisions in all cases.

In an effort to better define these conditions and to determine if such conditions constituted equivalent fire suppression capability, an additional detailed inspection was performed.

Guidelines were established for the inspection to assist the walkdown team in evaluating code variances and determining whether in a completed nuclear power plant adequate fire suppression capability is provided by the sprinkler systems as installed.

4 Page 2 The results of the walkdown are described as follows:

(1) Several cases were discovered where heads were lower than 12" from smooth ceilings (Code Provision).

In accordance with the established guidelines, a head which is within 3" of the code provision (or 15" down), APC0 proposes r.c modification.

For heads lower than 15" on smooth ceilines, A?CO proposes to raise the head to within 12" of the ceilicg provided no obstruction or other adverse fire suppression capability will result.

(2) Several cases were observed where heads were lower than 16" from beam and girder ceilings (Code Provision).

In accordance with the established guidelines, a head which is within 3" of the code provision (or 19" down), APC0 proposes no modification.

For heads lower than 19" on beam and girder ceilings, APC0 proposes to raise the head to within 16" of the ceiling provided no obstruction or other adverse fire suppression capability will result.

(3) Heads that were found to be obstructed and can be shifted to improve water distribution will be relocated.

If relocation of an obstructed head will not improve water distribution, APC0 proposes no modification.

(4) The Cable Spreading Room contains such massive congestion that heads are obstructed and are located farther from the ceiling than allowed by the code in many cases. APC0 does not propose any modifications for this room. A hot shutdown panel is currently under construction which will allow the plant to be brought to a safe shutdown condition with total loss of the Cable Spreading Room or Main Control Room.

Item 5.a (1) b (c) The sprinkler piping for the pre-action systems which contain over 20 heads are not supervised as cequired by Section 5-3.5.2 of NFPA-13.

Response

There e.re eleven (11) systems which contain over 20 heads and are presently not supervised. These systems will be modified to include air supervision.

Item 5.a (1) l (d) Test pipes (main drains) arranged to properly test the water ~ supply to each system are not provided as required by Section 2-9 of NFPA-13.

Response

In conjunction with tests of fire hose stations the test valves will 4

be partially opened to verify that flow connections are in order and no flow blockage exists.

Provisions will be made to ensure that plant equipment is properly protected from water damage during the tests.

APC0 will perform tests once every three years.

e Page 3 6

Item 5.a (1)

(e) Sprinkler heads of different orifice sizes (1/2 and 3/8 inch) are used to hydraulically balance the systems. This is clearly pro-hibited by Section 7-4.3.1.5 of NFPA-13.

Response

The issuance of replacement sprinkler heads will be controlled.

administratively to preclude inadvertent use of the incorrect orifice size.

ftem 5.a (1)

(f) The water spray system for the protection of motors at the service water intake structure utilizes closed type spray nozzles in lieu of the nonnally open type nozzles as required by Sections 1-3 and 2-3 of NFPA-15.

Response

Ten (10) pumps supply service water for both units. With an open type nozzle system, a fire associated with one (1) pump would cause all ten (10) pumps to be sprayed with water.

It is Alabama Power Company's position that impinging water on all ten (10) pumps at a smoke alarm signal would constitute a possible safety condition in that all motors would be subject to a potential electrical shortage due to water bombardment.

This is precluded by the use of fusable heads which would provide water only where necessary.

Further, it is anticipated that an oil type fire in this area would be of a sufficient temperature to readily fuse the low positioned heads.

Item 5.a (2) Exterior Fire Protection Water System Documentation was not available to verify that the underground fire protection piping from the Unit 1 fire loop to the service water intake structure was flushed as required.

Response

Since documentation was unavailable, Alabama Power Company has re-flushed the lines as necessary and associated documentation is avr'lable for review at Farley Nuclear Plant.

Item 5.b Fire Protection QA Program A review of the documentation available on the automatic sprinkler systems and the exterior fire protection piping (yard loop) installation indicate that QA documentation may not meet the requirements of the existing safety-related operational and con-struction QA programs.

The licensee has agreed to develop by June 1, 1980, a list of QA/QC documentation and record data which will be provided for all completed fire protection modifications and those modifications presently in process.

w- - -

Page 4

Response

This list has been developed and is available for review at Farley Nuclear Plant.

Item 5.c Fire Pump House The batteries and chargers for the diesel driven fire pump No.1 were found to be located in the enclosure for the electric driven fire pump and the start-stop switch for the electri.c fire pump was located in the enclosure for diesel fire pump Na.1.

Response

Production Change Requests (PCR's)80-623 and 80-628 have been issued to designers for evaluation and resolution of both problems.

..