Responds to to Dl Peoples Re SEP Topic 8-3.B,dc Power Sys Bus Voltage Monitoring & Annunciation. Typographical Error Noted in Section 5,Ref 2 Which Should Be Reg Guide 1.47 Not 1.74
ML19337A613
Person / Time
Site: Dresden 
Issue date: 09/17/1980
From: Janecek R
COMMONWEALTH EDISON CO.
To: Crutchfield D
Office of Nuclear Reactor Regulation
References
NUDOCS 8009290334
Download: ML19337A613 (1)


Text

__._

[CN Commonwealth Edison

) One First National Ptza, Chicigo, lilanois I

O" Address R; ply to: Post Offics Box 767

\\

Chicago. Illinois 60690 September 17, 1980 Dennis M.

Crutchfield, Chief Operating Reactors Branch #5 Division of Licensing U.S. Nuclear Regulatory Commission Washington, D.C.

20555

Subject:

Dresden 1 SEP Topic VIII - 3.8 D.C. Power System Bus Voltage Monitoring and Annunciation NRC Docket 50-10

Reference:

a)

Mr. Dennis M. Crutchfield's July 1,1980 letter to Me, D. Louis Peoples

Dear Mr. Crutchfield:

Commonwealth Edison has reviewed the Staff's evaluation of the above referenced topic.

There is a typographical error in Sectior. 5, Reference 2.

It should be Regulatory Guide 1.47 not 1.74.

The f actual inf ormation contained in the report is correct.

However, the report implies the two new systems installed in Dresden Unit 1 don't comply to IEEE 308-1974.

The new systems were designed to and comply with IEEE 308-1974.

The confusion about compliance with the IEEE standard is a result of the evaluation's Reference 3 which is an internal NRC document and a not a design guide nor a requirement.

Reference 3 which we have not reviewed, apparently requires considerably more indications and alarms be provided in the control room than IEEE 308-1974 req u i res.

The Dresden Unit 1 design provides sufficient inf ormation to the controlroom to alert the aperator to any problems but does not provide so much inf ormation as to saturate him.

If additional information is required to diagnose a problem on the D.C. systems it is available in the area the actual equipment is located.

Please address any questions you may have concerning this matter to this office.

One (1) signed original and thirty-nine (39) copies of this transmittal have been provided f or your use.

Very truly yours, Robert F. Janecek Nuclear Licensing cc: RIII Inspector - Dresden 1

g W ter Reactors NPS/ji 6760A